Trane Zone Controller, N512 manual Two-pipe heating/cooling unit with face-and-bypass damper

Models: Zone Controller CNT-SVX07C-EN N512

1 84
Download 84 pages 12.01 Kb
Page 42
Image 42

Chapter 4 Input/output functions and wiring for typical applications

Figure 16. Two-pipe heating/cooling unit with face-and-bypass damper

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

24 V

Fan, high speed

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

24 V

Heating/cooling isolation valve, open/close

 

 

24 V

 

 

 

Face-and-bypass damper actuator

 

 

 

24 V

 

 

 

Outdoor air damper actuator

Open

Close

Open Close

24 V

Generic/baseboard heat

 

 

 

Entering water

LonTalk temperature

Discharge air temperature

AI4 input: See

LonTalk

in

Figures 5 and 6

 

on page 20 for

 

wiring options

out

 

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.

32

CNT-SVX07C-EN

Page 42
Image 42
Trane Zone Controller, N512, CNT-SVX07C-EN manual Two-pipe heating/cooling unit with face-and-bypass damper