Chapter 7 Troubleshooting

Table 20. DX or electric heat does not energize (Continued)

Probable cause

Explanation

 

 

Requested mode off

You can communicate a desired operating mode (such as off, heat, and cool) to the con-

 

troller. If off is communicated to the controller, the unit shuts off the compressor or elec-

 

tric heat.

 

 

Freeze avoidance

When the fan is off with no demand for capacity (0%) and the outdoor air temperature is

 

below the freeze avoidance setpoint, the controller disables compressors and electric

 

heat outputs (100%) to prevent coil freezing. This includes unoccupied mode when there

 

is no call for capacity or any other time the fan is off.

 

 

Table 21. Outdoor air damper remains closed

Probable cause

Explanation

 

 

Unit wiring

The wiring between the controller outputs and the outdoor air damper must be present

 

and correct for normal outdoor air damper operation. Refer to applicable wiring diagram.

 

 

Failed end device

Check damper actuator to ensure proper operation.

 

 

No power to the

If the controller does not have power, the outdoor air damper does not operate. For the

controller

Tracer ZN521 controller to operate normally, you must apply an input voltage of 24 Vac. If

 

the green LED is off continuously, the controller does not have sufficient power or has

 

failed.

 

 

Diagnostic present

Several diagnostics affect outdoor air damper operation. For information about these

 

diagnostics, see Table 16 on page 59.

 

 

Normal

The controller opens and closes the outdoor air damper based on the controller’s occu-

operation

pancy mode and fan status. Normally, the outdoor air damper is open during occupied

 

mode when the fan is running and closed during unoccupied mode.

 

 

Unit configuration

The controller must be properly configured based on the actual installed end devices and

 

application. If the unit configuration does not match the actual end device, the outdoor air

 

damper may not work correctly.

 

 

Manual output test

The controller includes a manual output test sequence you can use to verify output oper-

 

ation and associated output wiring. However, based on the current step in the test

 

sequence, the outdoor air damper may not be open. Refer to the “Manual output test” on

 

page 52.

 

 

Warm-up and cool-

The controller includes both a morning warm-up and cool-down sequence to keep the

down sequence

outdoor air damper closed during the transition from unoccupied to occupied. This is an

 

attempt to bring the space under control as quickly as possible.

 

 

Requested mode off

You can communicate a desired operating mode (such as off, heat, or cool) to the control-

 

ler. If off is communicated to the controller, the unit closes the outdoor air damper.

 

 

Table 22. Outdoor air damper remains open

Probable cause

Explanation

 

 

Unit wiring

The wiring between the controller outputs and the outdoor air damper must be present

 

and correct for normal outdoor air damper operation. Refer to applicable wiring diagram.

 

 

Failed end device

Check damper actuator to ensure proper operation.

 

 