1 Basic Operation (continued)

1.3 Operating Principles

1.3.1 System Layout

MAIN

Q3

Manual Bypass

Circuit Breaker

 

Manual Input

 

 

 

Bypass Input

 

 

Q2

 

 

 

Bypass Input

STS

 

 

Circuit Breaker

 

 

 

 

 

 

Main

 

 

Q1

20kVA/3U POWER MODULE

Q4

LOAD

Main Input

 

Output

 

Circuit Breaker

 

Circuit Breaker

 

20kVA/3U POWER MODULE

20kVA/3U POWER MODULE

20kVA/3U POWER MODULE

BATTERY

Fig 1.3.1a System Block Diagram for KX models

Q3

Manual Bypass

Circuit Breaker

 

 

 

 

 

Manual Input

 

 

 

 

 

 

Bypass Input

 

 

 

 

 

 

STS

 

 

 

 

 

 

20kVA/3U POWER MODULE

LOAD

MAIN

Q2

XFMR

Q1

 

XFMR

 

Bypass Input

 

Main Input

 

Q4

 

Circuit Breaker

Circuit Breaker

20kVA/3U POWER MODULE

Output

 

 

 

 

 

Circuit Breaker

20kVA/3U POWER MODULE

20kVA/3U POWER MODULE

BATTERY

Fig 1.3.1b System Block Diagram for K and KTV models

The SU-Series 3-Phase UPS is configured with 3-phase 20kVA power modules that can be paralleled for redundancy or capacity upgrades. Each KX- (Figure 1.3.1a), K- , and KTV-series (Figure 1.3.1b) UPS includes three key functions:

1)A central bypass static switch, which causes a critical load to automatically bypass any overload or fault conditions that occur.

2)A maintenance bypass switch, which eliminates UPS faults by supplying a critical load.

3)A matched transformer, which increases and decreases the input/output voltage

1.3.2Internal Battery Layout

B+ N B-

12Vdc, 20pcs

12Vdc, 20pcs

Fig 1.3.2a Battery Strings

An internal battery pack (number of packs vary by model) supplies the UPS system with battery backup power. Each internal battery pack consists of 40 12Vdc VRLA batteries arranged in two strings: one string of 20 positive batteries (black cable) and one string of 20 negative batteries (red cable). The two strings are connected by a neutral (N) point (Figure 1.3.2a).

13

Page 13
Image 13
Tripp Lite SU60KX manual Operating Principles, System Layout, Internal Battery Layout