5 Troubleshooting (continued)

5.1 Alarm Messages (continued)

Alarm messages are displayed on the LCD control panel. Press the “UP” and “DOWN” buttons to scroll through all alarm messages.

Table 5.1b Power Module Warning Message List

Warning Message

Condition

 

 

PWR MODULE #n PFC FUSE OPEN

Power module #n main input fuse broken

 

 

PWR MODULE #n INVERTER FUSE OPEN

Power module #n output fuse broken

 

 

PWR MODULE #n GENERAL FAULT

PFC/INV control board fail

 

 

PWR MODULE #n CHARGER FAILURE

Power module #n charger board fail

 

 

PWR MODULE #n FAN FAILURE

Power module #n fan(s) fail

 

 

PWR MODULE #n PFC OVER TEMPERATURE WARNING

Power module #n PFC temperature over 60 degree C

 

 

PWR MODULE #n PFC OVER TEMPERATURE SHUTDOWN

Power module #n PFC temperature over 65 degree C

 

 

PWR MODULE #n INVERTER WARNING OVER TEMPERATURE

Power module #n INV temperature over 60 degree C

 

 

PWR MODULE #n INVERTER SHUTDOWN OVER TEMPERATURE

Power module #n INV temperature over 65 degree C

 

 

PWR MODULE #n INVERTER VOLT NOK

Power module #n INV voltage over rating ( 220V/230V/240V ) +/-1%

 

 

PWR MODULE #n INVERTER SHORT CIRCUIT

UPS output short circuit

 

 

PWR MODULE #n STATIC SWITCH FAULT

Power module #n STS open/short

 

 

PWR MODULE #n DC BUS ABNORMAL

Power module #n DC BUS over 430V / under 300V

 

 

Note: #n indicates the ID of the power module. (Ex.: #1 is power module 1)

Note: In the event of power module failure, refer to chapter 6.1.