1 Basic Operation

1.1 Technical Specifications

KX Models:

 

 

 

Model

SU20KX

SU40KX

 

SU60KX

SU80KX

 

 

 

(Capacity)

(20kVA/16kW)

(40kVA/32kW)

 

(60kVA/48kW)

(80kVA/64kW)

Input

Input Voltage

 

 

220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground, wye

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

 

 

-25% ~ +20%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harmonic Distortion

 

 

< 5% (Full Load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PFC (Full Load)

 

 

> 0.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

 

50 / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Tolerance

 

 

45 ~ 65 Hz

 

 

 

 

 

 

 

 

 

 

 

 

Output

Output Voltage

 

 

220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground, wye

 

 

 

 

 

 

 

 

 

 

Output Frequency

 

 

50 / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Harmonic (Linear Load)

3%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

Static

±1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dynamic

±7% (10% ~ 90% Linear Load)

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Regulation

Interior Oscillator

±0.05 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized

±5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

 

 

125% : 10 minutes; 150% : 1 minute

 

 

 

 

 

 

 

 

 

 

 

Audible Warning

Battery Backup

 

 

Intermittent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Abnormal

 

 

Continuous

 

 

 

 

 

 

 

 

 

 

 

 

Display

LED

 

 

UPS Status: Normal • Bypass • Backup • Fault

 

 

 

 

 

 

 

 

 

 

LCD

 

 

Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage

 

 

 

 

UPS abnormal messages with intelligent self-diagnosis.

 

 

 

 

 

 

 

 

 

 

Interface

Standard

 

 

RS-232, Dry Contact

 

 

 

 

 

 

 

 

 

 

 

 

Optional

 

 

SNMPWEBCARD

 

 

 

 

 

 

 

 

 

 

 

 

Others

Parallel Redundancy

 

 

Yes (1+1 for 2 UPS systems of the same type and capacity only.)

 

 

 

 

 

 

 

 

 

 

EPO

 

 

Standard (Local and Remote)

 

 

 

 

 

 

 

 

 

 

 

 

SRAM Event Log

 

 

500 Records

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Configuration

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Standby Installation

 

 

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Temperature Compensation

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Cold-Start

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

Overall

Efficiency

Normal

94%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECO

97%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer Time

 

 

0 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

32° F ~ 104° F (0° C ~ 40° C)

 

 

 

 

 

 

 

 

 

 

 

 

Humidity (non-condensing)

90%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise (1 m)

 

 

65 dBA

68 dBA

 

70 dBA

70 dBA

 

 

 

 

 

 

 

 

 

 

Dimensions (Power Module)

Width

520 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

850 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

1165 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight (Power Module)

 

 

267 kg*

412 kg*

 

210 kg

244 kg

 

 

 

 

 

 

 

 

 

3

Page 3
Image 3
Tripp Lite SU60KX manual Basic Operation, Technical Specifications, KX Models