5 Troubleshooting (continued)

5.2Troubleshooting Flow Charts (continued)

5.2.8“UPS INTERNAL COMM ABNORMAL”

Start

Has the

communication wire

slipped?(1)

Y

Re-insert communication wire and try again

END

N

Remove power connection of power module #1(2)

Still getting the

Y

same fault message?

 

N

Replace the power module

Re-insert power connection of previous power module and remove the next power module’s connection

Fig 5.2.8a

Note (1): Check W2A, W2B, W2C, W2D, W4A, W4B and W6 (Fig 5.2.8b).

Note (2): Remove wires W61A, W65A and W68A.

 

 

 

 

 

 

W3A

 

 

 

 

 

 

W2A

 

W4A

 

 

 

 

 

 

W5

 

W6

 

 

W61A

 

W65A

 

 

 

 

 

 

 

 

 

 

 

 

 

W68A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2B

 

 

 

 

 

 

W5

 

W6

 

 

 

 

 

 

W5

 

W6

 

 

W62B

 

W66B

 

 

 

 

 

 

 

 

 

 

 

 

W69B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2C

 

 

 

 

 

 

W5

 

W6

 

 

 

 

 

 

W5

 

W6

 

 

W63C

 

W67C

 

 

 

 

 

 

 

 

 

 

W70C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2D

 

 

 

 

 

 

W5

 

 

 

 

 

 

 

 

W6

 

 

 

 

 

 

W2B

 

 

 

 

 

W36D

 

 

W4B

 

 

W64D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W71D

 

 

 

 

 

 

 

 

Fig 5.2.8b