Tripp Lite SU60KX manual Start-Up, Shutdown and Bypass, Control Panel and Breaker Diagrams

Models: SU60KX

1 110
Download 110 pages 50.08 Kb
Page 18
Image 18

1 Basic Operation (continued)

1.6 Start-Up, Shutdown and Bypass

Warning: The UPS system’s output voltage is set at 220/380V by default. If you require output voltage of 230/400V or 240/415V, you must change the UPS system’s output voltage by accessing the output setup menu described in Section 10-9 of the owner’s manual. You must place the UPS system in bypass mode before changing the output voltage. Do not connect your equipment to the UPS system’s output until you have set the proper parameters.

1.6.1 Control Panel and Breaker Diagrams

“NORMAL” LED

“BATTERY” LED

“BYPASS” LED

“FAULT” LED

LCD Status Screen

“ESC” (Escape) Button

Scroll Buttons ( and )

Enter Button ( )

ON Button

OFF Button

“EPO” (Emergency Power Off) Button

Output Circuit Breaker Switch

Manual Bypass Circuit Breaker Switch

Bypass Input Circuit Breaker Switch

Main Input Circuit Breaker Switch

1.6.2 Preliminary Checklist (Single UPS)

E

F

I

K

A

 

 

 

B

G

 

 

C

 

 

 

 

 

D

 

 

 

1

H

J

 

 

 

 

Control Panel

L

M

N

O

Output

Manual

Bypass

Main

2

Bypass

Input

Input

Circuit Breaker Switches (UPS System Front Panel)

All circuit breaker switches should be off, including the breaker of the external battery cabinet (if present).

Confirm that no voltage potential exists between Neutral and Ground.

Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.

Note: After start-up, the UPS system will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS system will provide AC power to the connected equipment load.

1.6.3 Standard Start-Up Procedure (Single UPS)

If there is an external battery cabinet connected, switch on the circuit breaker of the external battery cabinet.

Confirm that the manual bypass circuit breaker switch is off.

A

1

 

A

 

 

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

18

Page 18
Image 18
Tripp Lite SU60KX Start-Up, Shutdown and Bypass, Control Panel and Breaker Diagrams, Preliminary Checklist Single UPS