3 Communication (continued)

3.1Setting EEPROM on the NH-M Board

3.1.1Polling and Updating EEPROM

WARNING: This procedure must be performed in bypass mode (see section 1.6).

Instructions for polling and updating the EEPROM are as follows (Figure 3.1.1a):

a)Link the UPS with a PC via the RS232 port

b)Run the program “NH_SYS_V1_3B1030.exe

c)Click the “EEPROM” icon

d)Select the PC COM Port and click “Open COM Port

e)Click “Polling” to download the EEPROM data from the UPS.

f)Save the file to ensure that you have the values in case they are needed later

g)After setting the data, click “Update All” and wait for the procedure to complete itself