2 Theory of Operation (continued)

2.19 Detection Circuit for Manual Bypass Switch

Located on NH-SYS-R board (Circuit for RS232, Output Dry Contact, Parallel Port, Connector to connect with each Power Module, Circuit for 2 Slots)

DR15

RR102

+12VSF

 

1

UR43

RR107

2

 

CR66

TOMBYP

CNR13

CR73

TO Manual Bypass Breaker

1

2

G4

Located on NH-SYS-M board (System MCU and Control Circuit)

RR103

5VS

4 #TOMBYP_I

3 CR65

G1

(6) TOMBYP I

RM146

#TOMBYP I

 

CM102

G1

(a)CNR13 connects to the auxiliary contact of the manual bypass switch.

(b)System MCU detects the status of the manual bypass switch via TOMBYP I (6). Manual bypass switch will stay in the OFF position and TOMBYO I (6) will be high.

2.20Detection Circuit for Output Breaker

Located on NH-SYS-R board (Circuit for RS232, Output Dry Contact, Parallel Port, Connector to connect with each Power Module, Circuit for 2 Slots)

+12VSF RR75

1 UR33

CR54 RR79 2

CNR10

CR58

1

 

2

 

 

G4

Located on NH-SYS-M board (System MCU and Control Circuit)

RR74

5VS

4 #OPCBAUX_I

3CR53

G1

(72) OPCBAUX_I

RM151

#OPCBAUX_I

 

CM108

G1

(a)CNR10 connects to the auxiliary contact of the output breaker.

(b)System MCU detects the status of the output breaker via OPCBAUX_I (72). Output breaker stays in the OFF position and OPCBAUX_I (72) will be high.