5 Troubleshooting

5.1 Alarm Messages

Alarm messages are displayed on the LCD control panel. Press the “UP” and “DOWN” buttons to scroll through all alarm messages.

Table 5.1a Warning Message List

Warning Message

Condition

Chapter Index

 

 

 

MAIN VOLT/FREQ NOK

Main input voltage abnormal

5.2.1

 

( load<70%: 120V~276V, load>70%:173V~276V )

 

 

Main input Freq. abnormal ( 45Hz~65Hz )

 

 

 

 

MAIN SEQUENCE NOK

Main input phase sequence abnormal

5.2.2

 

 

 

BYPASS VOLT/REQ NOK

Bypass voltage over rating

5.2.3

 

( 220V/230V/240V ) +/-15%

 

 

Bypass Freq. over rating ( 50Hz/60Hz )+/-5Hz

 

 

 

 

BYPASS SEQUENCE NOK

Bypass phase sequence abnormal

5.2.4

 

 

 

BYPASS STATIC SWITCH OVER TEMPERATURE

Bypass STS temperature over 80 degree C

5.2.5

 

 

 

BYPASS STATIC SWITCH FAULT

Bypass STS open/short

5.2.6

 

 

 

BYPASS STATIC SWITCH OVERLOAD

Bypass loading over 175%

5.2.7

 

 

 

UPS INTERNAL COMM ABNORMAL

1.CAN BUS loss

5.2.8

 

2.SCI loss

 

 

3.Power module internal communication loss

 

 

 

 

BAT TEST FAIL

Battery Capacity too low

5.2.9

 

 

 

BAT OVER CHARGE

Battery voltage more than 296V

5.2.10

 

 

 

BATTERY BAD

Battery Voltage under 190V

5.2.11

 

 

 

BYPASS FAN FAILURE

Bypass FanA/B/C fail

5.2.12

 

 

 

TRANSFORMER OVERHEAT

IN/OUT transformer overheat warning (HW detect signal)

5.2.13

 

 

 

UPS OUTPUT VOLT NOK

UPS output voltage over rating

5.2.14

 

( 220V/230V/240V ) +/-10V

 

 

 

 

UPS EXT PARALLEL COMM ABNORMAL

Parallel CAN BUS loss

5.2.15

 

 

 

PARALLEL FAILURE

PID confl ict or system KVA rating not the same

5.2.16

 

 

 

REDUNDANCY LOSS

UPS lost redundancy

5.2.17

 

 

 

MANUAL BYPASS ON

Manual bypass on

 

 

 

 

BAT LOW WARNING

Battery voltage under 220V and above 200V

 

 

 

 

BAT LOW SHUTDOWN

Battery voltage under 200V

 

 

 

 

BAT REPLACE REQUIRED

Battery package out of date

 

 

 

 

INVERTER OVERLOAD WARNING

Loading over 105%

 

 

 

 

INVERTER OVERLOAD SHUTDOWN

Loading over 105%~125% 10min.

 

 

Loading over 125%~150% 1min.

 

 

Loading over 150% 1sec.

 

 

 

 

INVERTER OVER CURRENT

Output current over 80A/phase

 

 

 

 

EMERGENCY POWER OFF ACTIVED

E.P.O./ Remote E.P.O. ON

 

 

 

 

OUTPUT BREAKER OFF

Output breaker not turn on

 

 

 

 

BYPASS LOAD OVER 104%

the load over 104% when UPS is on bypass

 

 

 

 

BAT CABINET OVER TEMPERATURE

Battery cabinet over 35 degree C

 

 

 

 

EXT BAT BREAKER OFF

If support external battery and the breaker ont turn on

 

 

 

 

98