5 Troubleshooting (continued)

5.2 Troubleshooting Flow Charts (continued)

5.2.16 “PARALLEL FAILURE”

Start

Are both

system’s EEPROM N power rating settings

the same?(1)

Y

Make sure that parallel

IDs(2) are different

END

Make sure the units

are identical. Synchronize power rating settings(1)

Fig 5.2.16a

Note (1): Figure 5.2.16b shows the EEPROM’s power rating settings (Rating VA). To learn about EEPROM parameter settings, turn to section 3.2.

Note (2): Access parallel ID settings using the LCD control panel (bypass mode only). (UPS SETUP LOCAL SETUP PARALLEL ID)

Fig 5.2.16b

112

Page 94
Image 94