5 Troubleshooting (continued)

5.2 Troubleshooting Flow Charts (continued)

5.2.3“BYPASS VOLT/FREQ NOK”

Start

Are the

the main or bypass N input circuit breaker

(Q1 and Q2)

turned on?

Turn on the main or

bypass input

circuit breaker

END

Fix the connection

Y

N

Are the

N

actual value and LCD value the same?

Y

 

 

Is the main input

Y

voltage or frequency

 

 

out of range?

 

N

Check the EEPROM voltage setting (2)

END

Y

Is the LCD value zero?

N

Replace P board or M

board(3) Calibrate parameter on

EEPROM(2)

Is the Wire #11(1) connection OK?

Y

Fig 5.2.3a

Note (1): For SU20KX, SU40KX and SU40K models, wire #11 is connected between P board (CNP8) and FA (CNA9) for bypass input. (See chapter 1.5.) For SU60KX, SU80KX, SU60K, SU80K, SU60KTV and SU80KTV, wire #11 is connected between P board (CNP8) and F1 (CNF15) for bypass input. (For locations, see chapter 1.7)

Note (2): To learn about EEPROM parameter settings and calibration, turn to chapter 3.2.

Note (3): For the location of the NHS-SYS-P and NHS-SYS-M boards, turn to chapter 1.5. To replace the NHS-SYS-M board, simply remove the EEPROM chip from an old NHS-SYS-M board and insert it into the new one.

M

P

Fig 5.2.3b

102

Page 84
Image 84
Tripp Lite SU60KX manual Bypass VOLT/FREQ NOK