1 Basic Operation (continued)

1.6 Start-Up, Shutdown and Bypass (continued)

1.6.3 Standard Start-Up Procedure (Single UPS) (continued)

Switch on the output circuit breaker switch and bypass input circuit breaker switch . After a brief initialization process, the LCD screen will show “ON AUTO BYPASS”, the “BYPASS” LED will illuminate and UPS system output will be supplied by the bypass (reserve) power source.

Switch on the main input circuit breaker switch . If the AC input power source is normal, the UPS system is ready for start-up.

Press the ON button for 3 seconds (until you hear a beep), then release the button. The inverter will activate and synchronize with the bypass source, then automatically switch from auto bypass (reserve) mode to online (normal) mode. The “BYPASS” LED will darken and the “NORMAL” LED will illuminate.

A

 

B

 

Output

Manual

Bypass

Main

3

Bypass

Input

Input

 

 

 

 

 

 

A

Output

Manual

Bypass

Main

4

Bypass

Input

Input

 

 

 

 

 

 

A

5

1.6.4 Battery Start-Up Procedure (Single UPS)

Note: The battery must be at least partially charged for this operation to succeed.

If there is an external battery cabinet connected, switch on the circuit breaker of the external battery cabinet.

Confirm that the manual bypass circuit breaker switch is off.

Press the ON button for 3 seconds (until you hear a beep), then release the button. The inverter will activate and use stored DC battery power to supply AC power to connected equipment. The “BATTERY” LED will illuminate.