1.1 Technical Specifications (continued)

 

 

SU80K Model:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model (Capacity)

SU80K (80kVA/64kW)

 

Input

 

 

Input Voltage

 

120/208V AC, 3Ø, 4-wire + ground, wye

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

 

-25% ~ +20%

 

 

 

 

Harmonic Distortion

 

< 5% (Full Load)

 

 

 

 

PFC (Full Load)

 

> 0.99

 

 

 

 

Frequency

 

50 / 60 Hz

 

 

 

 

Frequency Tolerance

 

45 ~ 65 Hz

 

 

 

 

 

 

 

 

Output

 

 

Output Voltage

 

120/208V AC, 3Ø, 4-wire + ground, wye

 

 

 

 

Output Frequency

 

50 / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

Total Harmonic (Linear Load)

 

3%

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

Static

±1%

 

 

 

 

 

 

 

 

 

 

 

 

Dynamic

±7% (10% ~ 90% Linear Load)

 

 

 

 

 

 

 

 

 

 

 

Frequency Regulation

Interior Oscillator

±0.05 Hz

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized

±5%

 

 

 

 

 

 

 

 

 

 

 

Overload

 

125% : 10 minutes; 150% : 1 minute

 

 

 

 

 

 

Audible Warning

Battery Backup

 

Intermittent

 

 

 

 

 

 

 

 

 

 

 

UPS Abnormal

 

Continuous

 

 

 

 

 

 

 

 

Display

 

 

LED

 

UPS Status: Normal • Bypass • Backup • Fault

 

 

 

 

 

 

 

 

 

 

 

LCD

 

Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage

 

 

 

 

 

 

UPS abnormal messages with intelligent self-diagnosis.

 

 

 

 

 

 

 

 

Interface

 

 

Standard

 

RS-232, Dry Contact

 

 

 

 

 

 

 

 

 

 

 

Optional

 

SNMPWEBCARD

 

 

 

 

 

 

 

 

Others

 

 

Parallel Redundancy

 

Yes (1+1 for 2 UPS systems of the same type and capacity only.)

 

 

 

 

 

 

 

 

 

 

 

EPO

 

Standard (Local and Remote)

 

 

 

 

 

 

 

 

 

 

 

SRAM Event Log

 

500 Records

 

 

 

 

 

 

 

 

 

 

 

Parameter Configuration

 

Yes

 

 

 

 

 

 

 

 

 

 

 

Hot Standby Installation

 

Optional

 

 

 

 

 

 

 

 

 

 

 

Battery Temperature Compensation

Optional

 

 

 

 

 

 

 

 

 

 

 

Battery Cold-Start

 

Standard

 

 

 

 

 

 

 

 

Overall

 

 

Efficiency

Normal

92%

 

 

 

 

 

 

 

 

 

 

 

 

ECO

96%

 

 

 

 

 

 

 

 

 

 

 

Transfer Time

 

0 ms

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

32° F ~ 104° F (0° C ~ 40° C)

 

 

 

 

 

 

 

 

 

 

 

Humidity (non-condensing)

 

90%

 

 

 

 

 

 

 

 

 

 

 

Noise (1 m)

 

70 dBA

 

 

 

 

Dimensions (Power Module)

Width

520 mm

 

 

 

 

 

Depth

1026 mm

 

 

 

 

 

Height

1696 mm

 

 

 

 

Weight (Power Module)

 

655 kg

 

 

 

 

 

 

 

 

5