Model MRC88

Page: 47

Figure 21

Figure 22

RS232 Palette Editor Window

Entering RS232 Command Strings

TESTING RS232 COMMAND STRINGS

There are two methods of testing RS232 Command Strings directly from the RS232 Palette Editor: One is directly out of the DragMRC PC’s Comport and the second method is through the MRC88’s RS232 Com Port – Figure 3-(29). Using both methods you can control the component or device directly for confirmation of command string or send the command to an RS232 Utility programming to verify proper output (this is good for Trouble Shooting purposes or for testing the program without the component or device present).

Using PC TEST:

1.Connect the Com Port of the PC running DragMRC to the corresponding component or device of the commands to be tested.

NOTE: A “Null Modem” cable may be necessary for communicating with the Component or Device. Please check with the Manufacturer to see if this is required.

2.Click on the ‘PC Test’ button in the RS232 Palette Editor.

3.Make sure the RS232 Port Settings are set appropriate for the device connected to (refer to the mfg’s Instruction Manual of the component or device being tested for the proper communication settings)

4.Click on the command string to be tested on the left-hand side of the RS232 Palette Editor. Note:

Only commands with the icon will be able to be tested.

5.The Device or Component connected should respond accordingly. If not, check the command string entered and port settings in the Test RS232 Settings window. If still having problems see the Trouble Shooting section to verify RS232 communication.

6.Test all Command Stings in this fashion before placing into a Palette File.

Using MRC88 TEST:

NOTE: The PC running DragMRC needs to connected to the programming port of the MRC88 Controller/Amplifier and communication verified (Base Unit “Who Am I”) before continuing.

1.Connect the Com Port on the rear of the MRC88 Controller/Amplifier – Figure 3-(29)to the corresponding component or device of the commands to be tested.

NOTE: A “Null Modem” cable may be necessary for communicating with the Component or Device. Please check with the Manufacturer to see if this is required (refer to MRC88 RS232 pin assignment as shown on page 97).

2.Click on the ‘MRC88 Test’ button in the RS232 Palette Editor.

3.Make sure the RS232 Port Settings (Baud Rate, Parity, Data Bits, and Stop Bits) are set appropriate for the device connected to (refer to the mfg’s Instruction Manual of the component or device being tested for the proper communication settings). Click on PREFERENCES and verify

© 2003 Xantech Corporation

Page 47
Image 47
Xantech mrc88 installation instructions RS232 Palette Editor Window, Using PC Test, Using MRC88 Test