Rack Mount Frame Assembly and Installation
User Line Connector
The
User Line Wiring
Use twisted pairs of
User Line Connection
Use this table to wire appropriate signals.
Table | User Line Connection |
|
| ||
|
|
|
|
|
|
Terminal | Label | I/O | Logic Level | Function | |
|
|
|
|
|
|
1 | User line return | GND | GND | GND reference | |
2 | User shutdown | Input | Active high | Shuts down | |
|
|
|
|
| inverter |
3 | Fault Flags | Output | Active high | Inverter faults | |
4 | AUX flag | Output | N/A | User configurable | |
5 | Inverter flag | Output | Active high | Inverter | |
6 | Not used | N/A | N/A | N/A | |
User line voltages are below: |
|
| |||
|
|
|
|
|
|
Inputs |
|
|
|
|
|
High | 1.25 V to 5 V |
|
|
|
|
Low | 0.0 V to 1.25 V |
|
|
|
|
|
|
|
|
|
|
Outputs |
|
|
|
|
|
High | 5 V |
|
|
|
|
Low | 1.5 V max. |
|
|
|
|
|
|
|
|
|
|