Operating Instructions
Automatic Shutdown Email
When the inverter shuts down due to a fault or a user shutdown, the Ethernet interface will attempt to send an email to the configured “Email Alert Address” using the configured “SMTP Server” (see “Network Connection” on page
Contents of the email:
From: XDI <serial number>
To: <Email Alert Address>
Subject: Unit has shutdown Body:
Serial # <Serial> at <IP> has shutdown. <Shutdown_Code>
The shutdown code list is a list of decimal values that represent specific shutdown conditions (Table
Important: By the time you have received the email, if the inverter has shutdown due to a fault, the inverter may have already corrected the problem.
Table | Shutdown Code |
|
|
Code | Fault Description |
|
|
16 | Reserved |
15 | Reserved |
14 | Reserved |
13 | Input stage voltage out of range |
12 | DC link stage over voltage |
11 | Output stage over voltage |
10 | Multiple output stage over current |
9 | Output overload |
8 | Synchronization error |
7 | Over temperature |
6 | Output disabled via interlock |
5 | Output disabled via interface command |
4 | Output disabled by user. (To enable, toggle interlock or interface command) |
3 | DC link stage under voltage |
2 | Output stage under voltage |
1 | Output stage over current |