Inverter Module Installation and Operation
Fuses and Grounding
The inverter is equipped with
XDI2048 120 V output: 20 A 250 V
XDI2048 230 V output: 12 A 250 V
Grounding studs are provided adjacent to the DC input and AC output ports. The equipment must be grounded at these locations as required by end applications and local regulations. See Chapter 2, “Rack Mount Frame Assembly and Installation” for connection details.
Incorrect Connection Protection
•Input contactor will not close for normal startup with reverse polarity input connection.
•The output contactor will not close if AC back feed is detected on power up or if a unit is unable to synchronize to the AC bus.
•The output fuse will open for output faults not covered by internal protection circuitry.
Output (AC) Alarm
The following conditions will cause an output alarm:
•Output overload
•Output short circuit
•Output
•
•Module failure
When such a condition exists,
1.The red FAULT indicator located on the front panel is turned on,
2.The open collector “Fault” alarm output is energized,
3.The output contactor is opened and the inverter output is disabled. Except in the case of an Output Overload when the module will continue to run for a short period, depending on the overload power, prior to shutdown.