Emerson 200, U/300/S/12P, 160 General Notes, Cable Connections, Safety Earth, Protective Devices

Page 26

16

Chapter 3 Electrical Installation

3.1.3 General Notes

The following are guidelines only and superseded by local regulations and codes of practice where applicable:

1.The neutral conductor should be sized for 1.5 times the output/bypass phase current.

2.The earth conductor should be sized at 2 times the output/bypass conductor (this is dependent on the fault rating, cable lengths, type of protection etc.).

3.Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.

4.When sizing battery cables, a maximum volt drop of 3Vdc is permissible at the current ratings given in Table 3-1.

5.In most installations, especially those concerning parallel multi-module systems, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output rather than being connected directly to the UPS itself. Where this is the case the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.

3.1.4Cable Connections

The rectifier input, bypass, output and battery power cables (all require lug type terminations) are connected to busbars situated below the power isolator switches, as shown in Figure 3-2 and Figure 3-3.

A terminal block X3 is used for connecting the control cables to the battery circuit breaker (BCB). These are female spade type connections (fast-on 6.3*0.8) and are described later in 3.3.2 Battery Control.

3.1.5 Safety Earth

The safety earth busbar is located near the input and output power supply connections as shown in Figure 3-2 and Figure 3-3. The safety earth cable must be connected to the earth busbar and bonded to each cabinet in the system.

All cabinets and cable trunking should be earthed in accordance with local regulations. The earth cable should be bound with binding strips onto the metallic column for cabling so as to prevent the fixing screw of the earth cable from loosening in the case the earth cable is pulled.

Warning

FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC SHOCK HAZARD TO PERSONNEL, OR THE RISK OF FIRE, SHOULD AN EARTH FAULT OCCUR.

3.1.6 Protective Devices

For safety reasons, it is necessary to install, external to the UPS system, circuit breaking protective devices in the input AC supply and towards the battery. Given that every installation has its own characteristics, this chapter provides general useful information for qualified installation engineers, with knowledge of operating practices, of regulatory standards, and of the equipment to be installed.

Rectifier and bypass input supply of the UPS

1. Protection against excessive overcurrents and short circuits in the mains supply input

These inputs must be protected, installing suitable protective devices at the distribution panel of the incoming mains supply, considering that the protection should discriminate with overload capacity of the system (see Table 8-6 and Table 8-7).

2. Split bypass

In the case of a split bypass being used, separate protective devices should be installed in the incoming mains distribution panel. The protective devices must be selected for the nominal input current, with respect to the UPS rating and the input AC supply voltage as given in Table 3-1.

3. Protection against earth faults

In the event of a residual current detector (RCD) device being installed upstream of the input supply, one must take into account the transient and steady state earth leakage currents that are produced during start-up of the UPS.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 26
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Design Concept FeaturesGeneral Description Hipulse U Module DesignNormal operation Bypass SuppliesSystem Control Philosophy Mains failureECO Mode For Single UPS Only Battery Circuit Breaker Operation ModeUPS Power Switch Configuration Battery Temperature CompensationMaintenance mode Auto-restart modeBypass mode Source Share modeUPS Location Mechanical InstallationEnvironmental Considerations Mechanical Considerations 1905 Front view Air inlet Installation DrawingsPreliminary Checks Top view Air651 761 800 843 Top view Air outlet615 556 1061 1210 1251 Side view Front view 1903 Air1641 Back view Top view Air outlet415 556 1451 1600 1641 Top view Air outlet 1685 1626 Cable access Base view104 424 155 Grille 2 pcs Front正view视图Removable Removable Grille 2 pcsAir inlet 进风口 Ventilation after being installedFront view 正视图 Grille System Configuration Electrical InstallationPower Cabling Cable RatingCable Connections Safety EarthGeneral Notes Protective DevicesNm M10 bolts. Ensure Correct Phase Rotation Cabling ProcedureUPS battery Output of the systemConnections Auxiliary Terminal blockRectifier Bypass Earth Distance From Floor To Connection Point Distance from floor to connection pointDry contact input ports Control CablingMonitoring Board Ports CardDescription of maintenance bypass cabinet port Dry contact output portCommunication ports Auxiliary DC power output portEPO input port Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesW45 Connecting Signal CablesPort side cabinet Cable No. main cabinet W41-5ULW36CSA8 Operator Control And Display Panel LED IndicatorsDescription of LED indicators IntroductionLCD And Menu Keys BuzzerControl Buttons Menu window and UPS data window Detailed Description Of Menu ItemsSystem information window Use the Shift key F1 and up and down arrow keys F2, F3 to Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Previously setBattery capacity test More Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times OK or FaultStart Screen LCD Screen TypesEPO Button Current record windowHelp Screen Default ScreenPrimary Screen Prompt Window UPS Alarm Message List Ongoing update of inverter firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of monitor firmwareIs found to be in error Can also leads to the alarmUnit over load timeout Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesLED status Start-Up Procedure Into Normal ModeStart-Up Procedure Into ECO Mode Battery test type and preconditions Battery Test Mode ProceduresSystem Test Procedure Test procedureLoad equipment is not protected from AC supply aberration Maintenance Bypass Procedure And UPS Shut DownShutdown Procedure Complete UPS And Load Shutdown EPO Procedure UPS Reset ProcedureChanging The Current Date And Time Auto RestartLanguage Selection UPS Batteries BatterySafety Temperature Considerations Installation Design ConsiderationsBattery Installation And Maintenance Battery PopulationBattery Installation Battery ProtectionBattery Connection Connecting The Battery738 BCB Box Optional455 654 1042Ф13 Knockout Battery Temperature Sensor Optional660 General 1+N System Installation Procedures+N System Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesInsertion Procedure Of One Module In a Parallel System Start-Up Procedure Into Normal ModeMaintenance Bypass Procedure And UPS Shut Down Bypass suppl y Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Input rectifier04115339 DB9-DB904115338 04116100 15m DB25-DB25Parallel cable UPS unit UPS parallel system LBS cableParallel board Board LBS cable Parallel并机board板Electrical Characteristics Input Rectifier SpecificationsMechanical Characteristics Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical characteristics inverter output Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics bypass input mainsElectrical characteristics system performance Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesReplacing Fuses Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Key components Life expectancyM10螺bolt栓 M12螺bolt栓 Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view RestraintAmplifiedA处放大图view 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer