5.10 Auto Restart

When the mains power fails, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.

The UPS will automatically restart and enable output power:

zAfter the mains power is restored.

zIf the Auto Recovery after EOD Enabling feature is enabled.

zAfter the Auto Recovery after EOD Delay Time expires (the default delay is 10 minutes) During the auto recovery delay, the UPS will be charging its batteries to provide a safety margin for equipment shutdown if input power fails again.

If the Auto Recovery after EOD Enabling feature is disabled, the user may restart the system manually by pressing the FAULT CLEAR button.

5.11 Language Selection

The LCD menus and data display are available in two languages: Chinese, English.

To select a different language than the one being displayed:

1.From the main menu, press the F1 (Shift) key to move the cursor to the menu at the top of the screen.

2.Press the F2 and F3 (left and right arrows) keys as needed to select the Language menu.

3.Press the F1 (Shift) key to move the cursor to the UPS Data Window of the LCD.

4.Use the F2 and F3 (up and down arrows) keys to select the required language.

5.Press the F4 (Enter) key to accept the language selection.

6.Return to the main menu by repeatedly pressing the F1 (ESC) key as needed; all text on the LCD will now be displayed in the selected language.

5.12Changing The Current Date And Time

To change the system date and time:

1.From the main menu, press the F1 (Shift) key to move the cursor to the menu at the top of the screen.

2.Press the F2 and F3 (left and right arrows) keys as needed to select the Settings menu.

3.Press the F1 (Shift) key to move the cursor to the UPS Data Window of the LCD.

4.Use the F2 and F3 (up and down arrows) keys to select the Date & time option, then press the F4 (Enter) key.

5.Position the cursor on the row in which the date and time are displayed, then press the F4 (Enter) key.

6.Using the F2 and F3 (up and down arrows) keys, enter the current time and date information.

7.Press the F4 (Enter) key to save the settings, and then press the F1 (ESC) key to return to the main menu.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 55
Contents 31011661 Version V1.0 Revision date April 29Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Hipulse U Module Design FeaturesGeneral Description Design ConceptMains failure Bypass SuppliesSystem Control Philosophy Normal operationECO Mode For Single UPS Only Battery Temperature Compensation Operation ModeUPS Power Switch Configuration Battery Circuit BreakerSource Share mode Auto-restart modeBypass mode Maintenance modeEnvironmental Considerations Mechanical InstallationUPS Location Mechanical Considerations Top view Air Installation DrawingsPreliminary Checks 1905 Front view Air inlet615 556 1061 1210 1251 Top view Air outlet651 761 800 843 Back view Top view Air outlet Front view 1903 Air1641 Side view104 424 155 Top view Air outlet 1685 1626 Cable access Base view415 556 1451 1600 1641 Removable Grille 2 pcs Front正view视图Removable Grille 2 pcsFront view 正视图 Ventilation after being installedAir inlet 进风口 Grille Cable Rating Electrical InstallationPower Cabling System ConfigurationProtective Devices Safety EarthGeneral Notes Cable ConnectionsOutput of the system Cabling ProcedureUPS battery Nm M10 bolts. Ensure Correct Phase RotationRectifier Bypass Earth Auxiliary Terminal blockConnections Distance from floor to connection point Distance From Floor To Connection PointCard Control CablingMonitoring Board Ports Dry contact input portsDry contact output port Description of maintenance bypass cabinet portDescription of dry contact output port Auxiliary DC power output portEPO input port Communication portsCommunication port resource deployment table Battery ControlConnecting Power Cables Connecting Main Cabinet And Side CabinetW41-5 Connecting Signal CablesPort side cabinet Cable No. main cabinet W45ULW36CSA8 Introduction LED IndicatorsDescription of LED indicators Operator Control And Display PanelControl Buttons BuzzerLCD And Menu Keys System information window Detailed Description Of Menu ItemsMenu window and UPS data window Previously set Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Use the Shift key F1 and up and down arrow keys F2, F3 toOK or Fault Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times Battery capacity test MoreCurrent record window LCD Screen TypesEPO Button Start ScreenPrimary Screen Default ScreenHelp Screen Prompt Window UPS Alarm Message List Ongoing update of monitor firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of inverter firmwareInverter overtemp Can also leads to the alarmUnit over load timeout Is found to be in errorTo this Operating Instructions Power SwitchesService, cannot be used for other purposes Service socket Designed for use in UPSStart-Up Procedure Into ECO Mode Start-Up Procedure Into Normal ModeLED status Test procedure Battery Test Mode ProceduresSystem Test Procedure Battery test type and preconditionsShutdown Procedure Complete UPS And Load Shutdown Maintenance Bypass Procedure And UPS Shut DownLoad equipment is not protected from AC supply aberration UPS Reset Procedure EPO ProcedureLanguage Selection Auto RestartChanging The Current Date And Time Safety BatteryUPS Batteries Battery Population Installation Design ConsiderationsBattery Installation And Maintenance Temperature ConsiderationsConnecting The Battery Battery ProtectionBattery Connection Battery Installation654 1042 BCB Box Optional455 738660 Battery Temperature Sensor OptionalФ13 Knockout Preliminary Checks 1+N System Installation Procedures+N System GeneralPower Cables Cabinet InstallationControl Cables 1+N System Operating InstructionsMaintenance Bypass Procedure And UPS Shut Down Start-Up Procedure Into Normal ModeInsertion Procedure Of One Module In a Parallel System Input rectifier Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Bypass suppl y04116100 15m DB25-DB25 DB9-DB904115338 04115339Parallel并机board板 LBS cableParallel board Board LBS cable Parallel cable UPS unit UPS parallel systemConformity And Standard SpecificationsMechanical Characteristics Electrical Characteristics Input RectifierElectrical characteristics DC intermediate circuit Electrical Characteristics DC Intermediate CircuitElectrical characteristics bypass input mains Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics inverter outputElectrical characteristics ECO mode Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics system performanceUPS Key Components And Their Lives Service & MaintenanceKey components Life expectancy Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Replacing FusesRestraint Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view M10螺bolt栓 M12螺bolt栓M10bolts螺栓 Output 输出变压器 transformer 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a AmplifiedA处放大图viewOpen the front door RemoveOpen thebackdoorpanel Phase 移相-shifting 变压 器Installation hole covers 400kVA UPS Transportation Restraints Removing ProceduresBolt 2 pcs Transportation restraint Bolt Phase-shiftingPhase-shifting transformer