Emerson U/300/S/6P, 400KVA Mechanical Installation, Environmental Considerations, UPS Location

Page 16

6

Chapter 2 Mechanical Installation

Chapter 2 Mechanical Installation

This chapter briefly introduces the mechanical installation of the HIPULSE U UPS, including the notes, environmental considerations, mechanical considerations, preliminary checks and installation drawings.

2.1 Notes

Warning

Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.

Warning

The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with details of its own mechanical and electrical installation.

Warning: battery hazards

Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal.

1.Eye protection should be worn to prevent injury from accidental electrical arcs.

2.Remove rings , watches and all metal objects.

3.Only use tools with insulated handles.

4.Wear rubber gloves.

5.If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

6.If electrolyte comes into contact with the skin the affected area should be washed immediately with water.

Warning

The UPS system can be connected to an isolated neutral (IT) power system.

This chapter describes the environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.

Because every site has its peculiarities, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide as to the general procedures and practices that should be observed by the installing engineer.

2.2 Environmental Considerations

2.2.1 UPS Location

The UPS module should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Table 8-2).

All models in the HIPULSE U UPS range are cooled with the aid of internal fans. Cooling air enters the module through ventilation grills located at various parts of the cabinet and exhausted through grills located in the cabinet roof. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS through the floor void. If necessary, a system of extractor fans should be installed to aid cooling-air flow, and a suitable air filtration system used where the UPS is to operate in a dirty environment.

Note:

1.When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS.

2.Power losses from the system which may be used in an air conditioning system are intended for operation using the inverter, as in the ECO mode configuration they would be undersized.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 16
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Features General DescriptionDesign Concept Hipulse U Module DesignBypass Supplies System Control PhilosophyNormal operation Mains failureECO Mode For Single UPS Only Operation Mode UPS Power Switch ConfigurationBattery Circuit Breaker Battery Temperature CompensationAuto-restart mode Bypass modeMaintenance mode Source Share modeEnvironmental Considerations Mechanical InstallationUPS Location Mechanical Considerations Installation Drawings Preliminary Checks1905 Front view Air inlet Top view Air615 556 1061 1210 1251 Top view Air outlet651 761 800 843 Front view 1903 Air 1641Side view Back view Top view Air outlet104 424 155 Top view Air outlet 1685 1626 Cable access Base view415 556 1451 1600 1641 Front正view视图 RemovableGrille 2 pcs Removable Grille 2 pcsFront view 正视图 Ventilation after being installedAir inlet 进风口 Grille Electrical Installation Power CablingSystem Configuration Cable RatingSafety Earth General NotesCable Connections Protective DevicesCabling Procedure UPS batteryNm M10 bolts. Ensure Correct Phase Rotation Output of the systemRectifier Bypass Earth Auxiliary Terminal blockConnections Distance From Floor To Connection Point Distance from floor to connection pointControl Cabling Monitoring Board PortsDry contact input ports CardDescription of maintenance bypass cabinet port Dry contact output portAuxiliary DC power output port EPO input portCommunication ports Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesConnecting Signal Cables Port side cabinet Cable No. main cabinetW45 W41-5ULW36CSA8 LED Indicators Description of LED indicatorsOperator Control And Display Panel IntroductionControl Buttons BuzzerLCD And Menu Keys System information window Detailed Description Of Menu ItemsMenu window and UPS data window Adjusts the graphic LCD monitor contrast for best viewing 中文/English Press the Enter key F4Use the Shift key F1 and up and down arrow keys F2, F3 to Previously setExplanation This setting applies to RS485 communication Communication mode RS232 Reserved Callback timesBattery capacity test More OK or FaultLCD Screen Types EPO ButtonStart Screen Current record windowPrimary Screen Default ScreenHelp Screen Prompt Window UPS Alarm Message List Alarm message Description Ongoing update of rectifier firmwareOngoing update of inverter firmware Ongoing update of monitor firmwareCan also leads to the alarm Unit over load timeoutIs found to be in error Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into ECO Mode Start-Up Procedure Into Normal ModeLED status Battery Test Mode Procedures System Test ProcedureBattery test type and preconditions Test procedureShutdown Procedure Complete UPS And Load Shutdown Maintenance Bypass Procedure And UPS Shut DownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureLanguage Selection Auto RestartChanging The Current Date And Time Safety BatteryUPS Batteries Installation Design Considerations Battery Installation And MaintenanceTemperature Considerations Battery PopulationBattery Protection Battery ConnectionBattery Installation Connecting The BatteryBCB Box Optional 455738 654 1042660 Battery Temperature Sensor OptionalФ13 Knockout 1+N System Installation Procedures +N SystemGeneral Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesMaintenance Bypass Procedure And UPS Shut Down Start-Up Procedure Into Normal ModeInsertion Procedure Of One Module In a Parallel System Dual Bus System Installation Procedures Shutdown Procedure Complete UPS And Load ShutdownBypass suppl y Input rectifierDB9-DB9 0411533804115339 04116100 15m DB25-DB25LBS cable Parallel board Board LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Specifications Mechanical CharacteristicsElectrical Characteristics Input Rectifier Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical Characteristics Inverter Output Electrical Characteristics Bypass Input MainsElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics System Performance Electrical Characteristics ECO ModeElectrical characteristics system performance Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesLives And Recommended Replacement Time Of Key Components Lifves and recommended replacement time of key componentsReplacing Fuses Key components Life expectancyAppendix 1 Transportation Restraints Removing Procedures 螺Screw钉 Amplified viewM10螺bolt栓 M12螺bolt栓 Restraint300kVA UPS Transportation Restraints Removing Procedures Output 输出变压器 transformer Phase-shifting aAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer