6 | Chapter 2 Mechanical Installation |
Chapter 2 Mechanical Installation
This chapter briefly introduces the mechanical installation of the HIPULSE U UPS, including the notes, environmental considerations, mechanical considerations, preliminary checks and installation drawings.
2.1 Notes
Warning
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
Warning
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with details of its own mechanical and electrical installation.
Warning: battery hazards
Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal.
1.Eye protection should be worn to prevent injury from accidental electrical arcs.
2.Remove rings , watches and all metal objects.
3.Only use tools with insulated handles.
4.Wear rubber gloves.
5.If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
6.If electrolyte comes into contact with the skin the affected area should be washed immediately with water.
Warning
The UPS system can be connected to an isolated neutral (IT) power system.
This chapter describes the environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site has its peculiarities, it is not the aim of this chapter to provide
2.2 Environmental Considerations
2.2.1 UPS Location
The UPS module should be located in a cool, dry,
All models in the HIPULSE U UPS range are cooled with the aid of internal fans. Cooling air enters the module through ventilation grills located at various parts of the cabinet and exhausted through grills located in the cabinet roof. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS through the floor void. If necessary, a system of extractor fans should be installed to aid
Note:
1.When batteries are
2.Power losses from the system which may be used in an air conditioning system are intended for operation using the inverter, as in the ECO mode configuration they would be undersized.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual