Emerson 400KVA Alarm message Description, Ongoing update of rectifier firmware, From the load

Page 46

36

Chapter 4 Operator Control And Display Panel

 

Alarm message

 

Description

 

REC FLASH UPDATE

Ongoing update of rectifier firmware

 

INV FLASH UPDATE

Ongoing update of inverter firmware

 

MONITOR FLASH

 

Ongoing update of monitor firmware

 

UPDATE

 

 

 

 

 

 

 

 

 

Unit off confirm

 

Prompt to press the Enter key (F4) to acknowledge that the UPS will be disconnected from other

 

 

paralleled UPS modules

 

 

 

 

 

 

 

 

System off confirm

 

Prompt to press the Enter key (F4) to acknowledge that the all paralleled UPS will be disconnected

 

 

from the load

 

 

 

 

Fault reset

 

FAULT CLEAR direct access key pressed

 

Alarm silence

 

SILENCE ON/OFF direct access key pressed

 

Turn on fail

 

Inverter failed to turn on when INVERTER ON direct access key was pressed. This may be as a

 

 

result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready

 

 

 

 

 

 

 

 

Alarm reset

 

FAULT CLEAR or SILENCE ON/OFF direct access key pressed

 

Transfer confirm

 

Prompt to press the Enter key (F4) to acknowledge that an interrupted load transfer to bypass will

 

 

happen

 

 

 

 

 

 

 

Transfer cancel

Prompt to press the ESC key (F4) to avoid that an interrupted load transfer to bypass will happen

 

Manual turn on

 

Manual Turn On through operator control and display panel

 

Manual turn off

 

Manual Turn Off through operator control and display panel

 

Battery ground fault

 

Battery leakage to ground detected (option)

 

Protocol version clash

Firmware incompatibility between Monitor Board and Digital Signal Processor Board

 

Setting save error

 

History records not saved. (Reserved)

 

Battery overtemp.

The Battery temperature is over limit. Check the battery temperature and ventilation

 

Ambient overtemp.

The Ambient temperature is over limit. Check the ventilation of UPS room

 

Battery fault

 

Battery detected faulty (Reserved)

 

Battery maintained

 

Battery test failed, Battery should be replaced

 

 

 

Before the end of discharge, battery undervoltage pre-warning should occur. After this pre-warning,

 

Battery low pre-warning

 

battery should have the capacity for 3 minutes discharging with full load. The time is user-configured

 

 

 

from 3 to 60 minutes. Shut down the load in time

 

 

 

 

 

Battery end of discharge

 

Inverter turned off due to low battery voltage. Check the utility failure and try to recover it

 

Inverter comm. fail

 

Internal RS485 communication failure between monitor and inverter

 

 

 

The CAN communication between different UPSs within a parallel system fails. 1.Check if there are

 

Parallel comm. fail

 

some UPSs not powered on in the parallel system. If so, power on these UPSs and check if the

 

 

 

alarm disappears. 2. Press the FAULT CLEAR push button

 

 

 

 

 

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass

 

 

 

voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10%

 

 

 

rating.

 

 

 

This alarm automatically resets once the bypass voltage goes normal. 1. First verify that the bypass

 

Bypass unable to trace

 

voltage and frequency displayed on the operator control and display panel is within the selected

 

 

 

range. Note here the rated voltage and frequency are specified by the system voltage level and

 

 

 

output frequency level respectively. 2. If the displayed voltage is believed to be abnormal, then verify

 

 

 

the bypass voltage and frequency presented to the UPS. Check the external supply if it is found to

 

 

 

be faulty

 

 

 

 

 

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass

 

 

 

voltage exceeds the limit. This alarm automatically resets once the bypass voltage goes normal.

 

 

 

First check if there are some relevant alarms such as Bypass disconnect open, Bypass phase

 

 

 

reverse. If they appear, solve them first. 1. Then verify that the bypass voltage and frequency

 

Bypass abnormal

 

displayed on the operator control and display panel is within the bypass limit. Note here the rated

 

 

voltage and frequency are specified by the system voltage level and output frequency level

 

 

 

 

 

 

respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage

 

 

 

and frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If

 

 

 

the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger

 

 

 

through the configuration software according to the customer’s agreement

 

 

 

 

 

 

 

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are

 

 

 

misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition is

 

Inverter asynchronous

 

no longer true. 1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so,

 

 

solve it first.

 

 

 

 

 

 

2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and seek

 

 

 

any possible measurements

 

Inverter output abnormal

 

Inverter output voltage beyond limits. Load transfers to bypass

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 46
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Design Concept FeaturesGeneral Description Hipulse U Module DesignNormal operation Bypass SuppliesSystem Control Philosophy Mains failureECO Mode For Single UPS Only Battery Circuit Breaker Operation ModeUPS Power Switch Configuration Battery Temperature CompensationMaintenance mode Auto-restart modeBypass mode Source Share modeEnvironmental Considerations Mechanical InstallationUPS Location Mechanical Considerations 1905 Front view Air inlet Installation DrawingsPreliminary Checks Top view Air615 556 1061 1210 1251 Top view Air outlet651 761 800 843 Side view Front view 1903 Air1641 Back view Top view Air outlet104 424 155 Top view Air outlet 1685 1626 Cable access Base view415 556 1451 1600 1641 Grille 2 pcs Front正view视图Removable Removable Grille 2 pcsFront view 正视图 Ventilation after being installedAir inlet 进风口 Grille System Configuration Electrical InstallationPower Cabling Cable RatingCable Connections Safety EarthGeneral Notes Protective DevicesNm M10 bolts. Ensure Correct Phase Rotation Cabling ProcedureUPS battery Output of the systemRectifier Bypass Earth Auxiliary Terminal blockConnections Distance From Floor To Connection Point Distance from floor to connection pointDry contact input ports Control CablingMonitoring Board Ports CardDescription of maintenance bypass cabinet port Dry contact output portCommunication ports Auxiliary DC power output portEPO input port Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesW45 Connecting Signal CablesPort side cabinet Cable No. main cabinet W41-5ULW36CSA8 Operator Control And Display Panel LED IndicatorsDescription of LED indicators IntroductionControl Buttons BuzzerLCD And Menu Keys System information window Detailed Description Of Menu ItemsMenu window and UPS data window Use the Shift key F1 and up and down arrow keys F2, F3 to Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Previously setBattery capacity test More Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times OK or FaultStart Screen LCD Screen TypesEPO Button Current record windowPrimary Screen Default ScreenHelp Screen Prompt Window UPS Alarm Message List Ongoing update of inverter firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of monitor firmwareIs found to be in error Can also leads to the alarmUnit over load timeout Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into ECO Mode Start-Up Procedure Into Normal ModeLED status Battery test type and preconditions Battery Test Mode ProceduresSystem Test Procedure Test procedureShutdown Procedure Complete UPS And Load Shutdown Maintenance Bypass Procedure And UPS Shut DownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureLanguage Selection Auto RestartChanging The Current Date And Time Safety BatteryUPS Batteries Temperature Considerations Installation Design ConsiderationsBattery Installation And Maintenance Battery PopulationBattery Installation Battery ProtectionBattery Connection Connecting The Battery738 BCB Box Optional455 654 1042660 Battery Temperature Sensor OptionalФ13 Knockout General 1+N System Installation Procedures+N System Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesMaintenance Bypass Procedure And UPS Shut Down Start-Up Procedure Into Normal ModeInsertion Procedure Of One Module In a Parallel System Bypass suppl y Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Input rectifier04115339 DB9-DB904115338 04116100 15m DB25-DB25Parallel cable UPS unit UPS parallel system LBS cableParallel board Board LBS cable Parallel并机board板Electrical Characteristics Input Rectifier SpecificationsMechanical Characteristics Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical characteristics inverter output Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics bypass input mainsElectrical characteristics system performance Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesReplacing Fuses Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Key components Life expectancyM10螺bolt栓 M12螺bolt栓 Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view RestraintAmplifiedA处放大图view 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer