Emerson 400KVA, U/300/S/12P EPO input port, Auxiliary DC power output port, Communication ports

Page 32

22

Chapter 3 Electrical Installation

Table 3-5 Description of dry contact output port

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay (NO)

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay (NC)

J21.2

INV_O

On inverter dry contact relay (NO)

J21.3

INV_S

On inverter dry contact relay center

J21.4

INV_C

On inverter dry contact relay (NC)

J25.2

ACF_O

Main input voltage or frequency fault relay (NO)

J25.3

ACF_S

Main input voltage or frequency fault relay center

J25.4

ACF_C

Main input voltage or frequency fault relay (NC)

 

 

 

Note

All auxiliary cables must be double insulated. Wire should be 0.5~1.5mm2 stranded.

EPO input port (X2)

The UPS has an Emergency Power Off (EPO) function that operates by a button on the UPS door or by a remote contact provided by the user.

The X2 slot, shown in Figure 3-7, is the remote EPO input port, which is described in Table 3-6.

Figure 3-7 EPO input port

Table 3-6 Description of EPO input port

Position

Name

Description

J28.1

EPO_NC

EPO activated when opened to J28.2

J28.2

EPO_NC

EPO activated when opened to J28.1

J28.3

EPO_NO

EPO activated when shorted to J28.4

J28.4

EPO_NO

EPO activated when shorted to J28.3

The remote EPO facility is connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable. If this function is not used, terminals J28: 3&4 must be opened and J28: 1&2 must be closed.

Note

The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.

Normally closed EPO–J28: 1, 2, these terminals are supplied factory-linked on the monitor board.

Auxiliary DC power output port (X5)

The auxiliary DC power output port X5 provides auxiliary DC power for optional SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA.

Communication ports

The communication ports include the serial ports RS232-1 and RS232-2, Intellislot intelligent communication ports. 1. Serial ports RS232-1 and RS232-2

RS232-1 provides serial data and is intended for direct use with Emerson UPSitePlusTM UPS monitoring software. RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 32
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Features General DescriptionDesign Concept Hipulse U Module DesignBypass Supplies System Control PhilosophyNormal operation Mains failureECO Mode For Single UPS Only Operation Mode UPS Power Switch ConfigurationBattery Circuit Breaker Battery Temperature CompensationAuto-restart mode Bypass modeMaintenance mode Source Share modeUPS Location Mechanical InstallationEnvironmental Considerations Mechanical Considerations Installation Drawings Preliminary Checks1905 Front view Air inlet Top view Air651 761 800 843 Top view Air outlet615 556 1061 1210 1251 Front view 1903 Air 1641Side view Back view Top view Air outlet415 556 1451 1600 1641 Top view Air outlet 1685 1626 Cable access Base view104 424 155 Front正view视图 RemovableGrille 2 pcs Removable Grille 2 pcsAir inlet 进风口 Ventilation after being installedFront view 正视图 Grille Electrical Installation Power CablingSystem Configuration Cable RatingSafety Earth General NotesCable Connections Protective DevicesCabling Procedure UPS batteryNm M10 bolts. Ensure Correct Phase Rotation Output of the systemConnections Auxiliary Terminal blockRectifier Bypass Earth Distance From Floor To Connection Point Distance from floor to connection pointControl Cabling Monitoring Board PortsDry contact input ports CardDescription of maintenance bypass cabinet port Dry contact output portAuxiliary DC power output port EPO input portCommunication ports Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesConnecting Signal Cables Port side cabinet Cable No. main cabinetW45 W41-5ULW36CSA8 LED Indicators Description of LED indicatorsOperator Control And Display Panel IntroductionLCD And Menu Keys BuzzerControl Buttons Menu window and UPS data window Detailed Description Of Menu ItemsSystem information window Adjusts the graphic LCD monitor contrast for best viewing 中文/English Press the Enter key F4Use the Shift key F1 and up and down arrow keys F2, F3 to Previously setExplanation This setting applies to RS485 communication Communication mode RS232 Reserved Callback timesBattery capacity test More OK or FaultLCD Screen Types EPO ButtonStart Screen Current record windowHelp Screen Default ScreenPrimary Screen Prompt Window UPS Alarm Message List Alarm message Description Ongoing update of rectifier firmwareOngoing update of inverter firmware Ongoing update of monitor firmwareCan also leads to the alarm Unit over load timeoutIs found to be in error Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesLED status Start-Up Procedure Into Normal ModeStart-Up Procedure Into ECO Mode Battery Test Mode Procedures System Test ProcedureBattery test type and preconditions Test procedureLoad equipment is not protected from AC supply aberration Maintenance Bypass Procedure And UPS Shut DownShutdown Procedure Complete UPS And Load Shutdown EPO Procedure UPS Reset ProcedureChanging The Current Date And Time Auto RestartLanguage Selection UPS Batteries BatterySafety Installation Design Considerations Battery Installation And MaintenanceTemperature Considerations Battery PopulationBattery Protection Battery ConnectionBattery Installation Connecting The BatteryBCB Box Optional 455738 654 1042Ф13 Knockout Battery Temperature Sensor Optional660 1+N System Installation Procedures +N SystemGeneral Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesInsertion Procedure Of One Module In a Parallel System Start-Up Procedure Into Normal ModeMaintenance Bypass Procedure And UPS Shut Down Dual Bus System Installation Procedures Shutdown Procedure Complete UPS And Load ShutdownBypass suppl y Input rectifierDB9-DB9 0411533804115339 04116100 15m DB25-DB25LBS cable Parallel board Board LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Specifications Mechanical CharacteristicsElectrical Characteristics Input Rectifier Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical Characteristics Inverter Output Electrical Characteristics Bypass Input MainsElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics System Performance Electrical Characteristics ECO ModeElectrical characteristics system performance Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesLives And Recommended Replacement Time Of Key Components Lifves and recommended replacement time of key componentsReplacing Fuses Key components Life expectancyAppendix 1 Transportation Restraints Removing Procedures 螺Screw钉 Amplified viewM10螺bolt栓 M12螺bolt栓 Restraint300kVA UPS Transportation Restraints Removing Procedures Output 输出变压器 transformer Phase-shifting aAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer