Emerson 400KVA, U/300/S/12P, U /400/S/12P Battery Temperature Sensor Optional, 660, Ф13 Knockout

Page 60

50

Chapter 6 Battery

660

167

4-Ф13 Knockout

Figure 6-4 Installation hole dimensions for floor mounting of BCB box of 300/400kVA UPS (unit: mm)

The battery circuit breaker (BCB) box contains a BCB and a BCB control board (ULK366SC1).

The BCB box is fitted as close as possible to the battery and connected to the UPS, as illustrated in Figure 6-5.

 

UPS

 

 

 

 

 

FB

 

BCB status feedback

GND

 

BCB connection detection

 

OL

 

 

+12V

 

Battery temperature sensing 1

 

TMP_T

 

 

GND

 

Battery temperature sensing 2

 

LM355+

 

 

LM355+ GND

 

 

BCB drive

 

DRV

 

 

 

DRV_ GND

 

Not connected

NC

 

NC

 

 

 

 

 

BCB control board

TMP12Z

TMP12Z

TMP12Z

TMP12Z

Figure 6-5 BCB box connection

Note: The control cables from the UPS to the BCB control board must be made using the accessory cable of the BCB, which is a shielded cable located in a separate conduit to that containing the battery power cables. The cable shield must be earthed to prevent induced noise affecting the control operation, and a separate safety earth must be connected between the UPS and BCB box.

6.10 Battery Temperature Sensor (Optional)

A battery temperature sensor (model: TMP12Z) supplied separately from the BCB is connected with the UPS logic through the BCB control board. For the connection, see Figure 6-5.

With this feature fitted, the nominal float voltage supplied to the battery is adjusted so as to be inversely proportional to the ambient temperature of the battery cabinet or battery room. This prevents the battery being over charged at high ambient temperatures.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 60
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Features General DescriptionDesign Concept Hipulse U Module DesignBypass Supplies System Control PhilosophyNormal operation Mains failureECO Mode For Single UPS Only Operation Mode UPS Power Switch ConfigurationBattery Circuit Breaker Battery Temperature CompensationAuto-restart mode Bypass modeMaintenance mode Source Share modeMechanical Installation Environmental ConsiderationsUPS Location Mechanical Considerations Installation Drawings Preliminary Checks1905 Front view Air inlet Top view AirTop view Air outlet 615 556 1061 1210 1251651 761 800 843 Front view 1903 Air 1641Side view Back view Top view Air outletTop view Air outlet 1685 1626 Cable access Base view 104 424 155415 556 1451 1600 1641 Front正view视图 RemovableGrille 2 pcs Removable Grille 2 pcsVentilation after being installed Front view 正视图Air inlet 进风口 Grille Electrical Installation Power CablingSystem Configuration Cable RatingSafety Earth General NotesCable Connections Protective DevicesCabling Procedure UPS batteryNm M10 bolts. Ensure Correct Phase Rotation Output of the systemAuxiliary Terminal block Rectifier Bypass EarthConnections Distance From Floor To Connection Point Distance from floor to connection pointControl Cabling Monitoring Board PortsDry contact input ports CardDescription of maintenance bypass cabinet port Dry contact output portAuxiliary DC power output port EPO input portCommunication ports Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesConnecting Signal Cables Port side cabinet Cable No. main cabinetW45 W41-5ULW36CSA8 LED Indicators Description of LED indicatorsOperator Control And Display Panel IntroductionBuzzer Control ButtonsLCD And Menu Keys Detailed Description Of Menu Items System information windowMenu window and UPS data window Adjusts the graphic LCD monitor contrast for best viewing 中文/English Press the Enter key F4Use the Shift key F1 and up and down arrow keys F2, F3 to Previously setExplanation This setting applies to RS485 communication Communication mode RS232 Reserved Callback timesBattery capacity test More OK or FaultLCD Screen Types EPO ButtonStart Screen Current record windowDefault Screen Primary ScreenHelp Screen Prompt Window UPS Alarm Message List Alarm message Description Ongoing update of rectifier firmwareOngoing update of inverter firmware Ongoing update of monitor firmwareCan also leads to the alarm Unit over load timeoutIs found to be in error Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into Normal Mode Start-Up Procedure Into ECO ModeLED status Battery Test Mode Procedures System Test ProcedureBattery test type and preconditions Test procedureMaintenance Bypass Procedure And UPS Shut Down Shutdown Procedure Complete UPS And Load ShutdownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureAuto Restart Language SelectionChanging The Current Date And Time Battery SafetyUPS Batteries Installation Design Considerations Battery Installation And MaintenanceTemperature Considerations Battery PopulationBattery Protection Battery ConnectionBattery Installation Connecting The BatteryBCB Box Optional 455738 654 1042Battery Temperature Sensor Optional 660Ф13 Knockout 1+N System Installation Procedures +N SystemGeneral Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesStart-Up Procedure Into Normal Mode Maintenance Bypass Procedure And UPS Shut DownInsertion Procedure Of One Module In a Parallel System Dual Bus System Installation Procedures Shutdown Procedure Complete UPS And Load ShutdownBypass suppl y Input rectifierDB9-DB9 0411533804115339 04116100 15m DB25-DB25LBS cable Parallel board Board LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Specifications Mechanical CharacteristicsElectrical Characteristics Input Rectifier Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical Characteristics Inverter Output Electrical Characteristics Bypass Input MainsElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics System Performance Electrical Characteristics ECO ModeElectrical characteristics system performance Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesLives And Recommended Replacement Time Of Key Components Lifves and recommended replacement time of key componentsReplacing Fuses Key components Life expectancyAppendix 1 Transportation Restraints Removing Procedures 螺Screw钉 Amplified viewM10螺bolt栓 M12螺bolt栓 Restraint300kVA UPS Transportation Restraints Removing Procedures Output 输出变压器 transformer Phase-shifting aAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer