Emerson U/300/S/12P, U /400/S/12P, U/300/S/6P, 400KVA Electrical Characteristics Inverter Output

Page 70

60

Chapter 8 Specifications

8.6 Electrical Characteristics (Inverter Output)

Table 8-6 Electrical characteristics (inverter output)

 

 

Item

 

 

Unit

 

 

 

 

 

Power rating (kVA)

 

 

 

 

 

 

 

 

 

160

 

 

200

 

 

300

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated mains voltage1

 

Vac

 

 

 

 

380, 400, or 415

 

 

 

 

Supply

-

 

 

 

 

 

Three phase with neutral

 

 

 

 

Frequency2

 

Hz

 

 

 

 

 

50 or 60

 

 

 

 

Rated Power at cos = 0.9

 

kVA

 

160

 

200

 

300

 

400

 

 

Rated Power at cos = 1

 

kW

 

144

 

180

 

270

 

360

 

 

 

 

 

 

Min,

 

 

 

 

 

60,

1.10

 

 

 

 

 

Three-phase transient overload3

 

 

 

 

 

 

10, 1.25

 

 

 

 

 

 

I/In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1, 1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximal non linear load allowed4

-

 

 

 

 

 

 

100%Pn

 

 

 

 

Voltage stability, steady State test3

%

 

 

 

 

 

 

±1

 

 

 

 

 

 

Voltage stability, transient test 5

%

 

 

 

 

 

 

±5

 

 

 

 

 

 

Maximum rate of charge of frequency6

 

Hz/s

 

 

 

 

 

0.1

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Factory set 380V 400 or 415 voltages with software setting.

 

 

 

 

 

 

 

 

 

2.

Factory set at 50Hz 60 Hz with software setting.

 

 

 

 

 

 

 

 

 

 

 

3.

IEC62040-3 (5.3.2).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

IEC62040-3 (ANNEX E).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

IEC62040-3 (5.3.1), also for 0~100~0%, load transient, restore time 20 ms to 1%.

 

 

 

 

 

 

 

6.

Factory set at 0.1Hz/s; up to 1Hz/s with software setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.7 Electrical Characteristics (Bypass Input Mains)

Table 8-7 Electrical characteristics (bypass input mains)

 

Item

 

 

Unit

 

 

 

 

 

 

Power rating (kVA)

 

 

 

 

 

 

 

 

 

 

 

160

 

 

200

 

 

 

 

300

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated mains voltage1

 

Vac

 

 

 

 

 

380, 400, or 415

 

 

 

 

 

 

 

 

Supply

-

 

 

 

 

 

 

Three phase with neutral

 

 

 

 

 

 

 

Rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380Vac

 

A

 

243

 

 

304

 

 

 

 

456

 

 

 

607

 

 

400Vac

 

 

231

 

 

289

 

 

 

 

433

 

 

 

577

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

416

 

 

 

 

 

 

 

 

 

 

 

222

 

 

278

 

 

 

 

 

 

 

554

 

 

Bypass voltage tolerance2

%

 

 

 

 

Default upper limit: 15%; default lower limit: -20%

 

 

 

 

Delay time to recognise bypass

 

s

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

voltage returned to window

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter output voltage window

%

 

 

 

 

 

 

 

±5

 

 

 

 

 

 

 

 

 

 

Frequency3

 

Hz

 

 

 

 

 

 

50 or 60

 

 

 

 

 

 

 

 

Input frequency tolerance 4

%

 

 

 

 

 

 

 

±5

 

 

 

 

 

 

 

 

 

 

Maximum frequency slew rate

 

Hz/s

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

Current rating of neutral cable

-

 

 

 

 

 

 

 

1.3In

 

 

 

 

 

 

 

 

Protection, bypass line

-

 

The bypass line should be protected using an external device in the input distribution

 

 

system. This device should be sized to discriminate with the load protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transient overload

 

ms

10

 

20

50

100

200

 

500

1000

2000

 

5000

 

 

I/In

14.3

 

12.6

11.0

10.0

9.0

 

8.0

7.1

 

6.6

 

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

1.Factory set 380V. 400 or 415 voltages with software setting.

2.Other values in -20%~15% with software setting.

3.Factory set at 50Hz 60 Hz with software setting.

4.Other values -5%~5%with software setting

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 70
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Design Concept FeaturesGeneral Description Hipulse U Module DesignNormal operation Bypass SuppliesSystem Control Philosophy Mains failureECO Mode For Single UPS Only Battery Circuit Breaker Operation ModeUPS Power Switch Configuration Battery Temperature CompensationMaintenance mode Auto-restart modeBypass mode Source Share modeEnvironmental Considerations Mechanical InstallationUPS Location Mechanical Considerations 1905 Front view Air inlet Installation DrawingsPreliminary Checks Top view Air615 556 1061 1210 1251 Top view Air outlet651 761 800 843 Side view Front view 1903 Air1641 Back view Top view Air outlet104 424 155 Top view Air outlet 1685 1626 Cable access Base view415 556 1451 1600 1641 Grille 2 pcs Front正view视图Removable Removable Grille 2 pcsFront view 正视图 Ventilation after being installedAir inlet 进风口 Grille System Configuration Electrical InstallationPower Cabling Cable RatingCable Connections Safety EarthGeneral Notes Protective DevicesNm M10 bolts. Ensure Correct Phase Rotation Cabling ProcedureUPS battery Output of the systemRectifier Bypass Earth Auxiliary Terminal blockConnections Distance From Floor To Connection Point Distance from floor to connection pointDry contact input ports Control CablingMonitoring Board Ports CardDescription of maintenance bypass cabinet port Dry contact output portCommunication ports Auxiliary DC power output portEPO input port Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesW45 Connecting Signal CablesPort side cabinet Cable No. main cabinet W41-5ULW36CSA8 Operator Control And Display Panel LED IndicatorsDescription of LED indicators IntroductionControl Buttons BuzzerLCD And Menu Keys System information window Detailed Description Of Menu ItemsMenu window and UPS data window Use the Shift key F1 and up and down arrow keys F2, F3 to Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Previously setBattery capacity test More Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times OK or FaultStart Screen LCD Screen TypesEPO Button Current record windowPrimary Screen Default ScreenHelp Screen Prompt Window UPS Alarm Message List Ongoing update of inverter firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of monitor firmwareIs found to be in error Can also leads to the alarmUnit over load timeout Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into ECO Mode Start-Up Procedure Into Normal ModeLED status Battery test type and preconditions Battery Test Mode ProceduresSystem Test Procedure Test procedureShutdown Procedure Complete UPS And Load Shutdown Maintenance Bypass Procedure And UPS Shut DownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureLanguage Selection Auto RestartChanging The Current Date And Time Safety BatteryUPS Batteries Temperature Considerations Installation Design ConsiderationsBattery Installation And Maintenance Battery PopulationBattery Installation Battery ProtectionBattery Connection Connecting The Battery738 BCB Box Optional455 654 1042660 Battery Temperature Sensor OptionalФ13 Knockout General 1+N System Installation Procedures+N System Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesMaintenance Bypass Procedure And UPS Shut Down Start-Up Procedure Into Normal ModeInsertion Procedure Of One Module In a Parallel System Bypass suppl y Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Input rectifier04115339 DB9-DB904115338 04116100 15m DB25-DB25Parallel cable UPS unit UPS parallel system LBS cableParallel board Board LBS cable Parallel并机board板Electrical Characteristics Input Rectifier SpecificationsMechanical Characteristics Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical characteristics inverter output Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics bypass input mainsElectrical characteristics system performance Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesReplacing Fuses Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Key components Life expectancyM10螺bolt栓 M12螺bolt栓 Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view RestraintAmplifiedA处放大图view 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer