Chapter 3 Electrical Installation

6.Connect the system output cables between the output busbars (N3-U3-V3-W3 terminals) and the critical load and tighten the connections to 13 Nm (M8 bolt), to 26 Nm (M10 bolt), and to 50 Nm (M12 bolt). ENSURE CORRECT PHASE ROTATION.

Warning

If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then ensure that the system output cables are safely isolated at their ends.

UPS Battery Connections

7.Connect the battery cables between the UPS terminals (+/-) and its associated BCB. Connect screened auxiliary cables from each BCB control board to the auxiliary terminal block (X3). OBSERVE THE BATTERY CABLE POLARITY.

Warning

Do not close the BCB before the equipment has been commissioned.

8. Refit the lower protective cover.

Note: For split bypass operation, ensure that the busbars ( ) between the bypass input and rectifier input are removed.

Auxiliary

terminal block

X3

 

 

Q1

 

 

 

Q2

 

 

 

Q5

 

 

 

 

 

 

*

 

 

 

 

Q3

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

U1

V1

W1

N1

U2

V2

W2

N2

N3

U3

V3

W3

Battery

Rectifier

 

Bypass

Earth

Output

connections

connections

connections

connections

Figure 3-2 Power cable connections for 160/200kVA UPS

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 28
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Features General DescriptionDesign Concept Hipulse U Module DesignBypass Supplies System Control PhilosophyNormal operation Mains failureECO Mode For Single UPS Only Operation Mode UPS Power Switch ConfigurationBattery Circuit Breaker Battery Temperature CompensationAuto-restart mode Bypass modeMaintenance mode Source Share modeEnvironmental Considerations Mechanical InstallationUPS Location Mechanical Considerations Installation Drawings Preliminary Checks1905 Front view Air inlet Top view Air615 556 1061 1210 1251 Top view Air outlet651 761 800 843 Front view 1903 Air 1641Side view Back view Top view Air outlet104 424 155 Top view Air outlet 1685 1626 Cable access Base view415 556 1451 1600 1641 Front正view视图 RemovableGrille 2 pcs Removable Grille 2 pcsFront view 正视图 Ventilation after being installedAir inlet 进风口 Grille Electrical Installation Power CablingSystem Configuration Cable RatingSafety Earth General NotesCable Connections Protective DevicesCabling Procedure UPS batteryNm M10 bolts. Ensure Correct Phase Rotation Output of the systemRectifier Bypass Earth Auxiliary Terminal blockConnections Distance From Floor To Connection Point Distance from floor to connection pointControl Cabling Monitoring Board PortsDry contact input ports CardDescription of maintenance bypass cabinet port Dry contact output portAuxiliary DC power output port EPO input portCommunication ports Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesConnecting Signal Cables Port side cabinet Cable No. main cabinetW45 W41-5ULW36CSA8 LED Indicators Description of LED indicatorsOperator Control And Display Panel IntroductionControl Buttons BuzzerLCD And Menu Keys System information window Detailed Description Of Menu ItemsMenu window and UPS data window Adjusts the graphic LCD monitor contrast for best viewing 中文/English Press the Enter key F4Use the Shift key F1 and up and down arrow keys F2, F3 to Previously setExplanation This setting applies to RS485 communication Communication mode RS232 Reserved Callback timesBattery capacity test More OK or FaultLCD Screen Types EPO ButtonStart Screen Current record windowPrimary Screen Default ScreenHelp Screen Prompt Window UPS Alarm Message List Alarm message Description Ongoing update of rectifier firmwareOngoing update of inverter firmware Ongoing update of monitor firmwareCan also leads to the alarm Unit over load timeoutIs found to be in error Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into ECO Mode Start-Up Procedure Into Normal ModeLED status Battery Test Mode Procedures System Test ProcedureBattery test type and preconditions Test procedureShutdown Procedure Complete UPS And Load Shutdown Maintenance Bypass Procedure And UPS Shut DownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureLanguage Selection Auto RestartChanging The Current Date And Time Safety BatteryUPS Batteries Installation Design Considerations Battery Installation And MaintenanceTemperature Considerations Battery PopulationBattery Protection Battery ConnectionBattery Installation Connecting The BatteryBCB Box Optional 455738 654 1042660 Battery Temperature Sensor OptionalФ13 Knockout 1+N System Installation Procedures +N SystemGeneral Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesMaintenance Bypass Procedure And UPS Shut Down Start-Up Procedure Into Normal ModeInsertion Procedure Of One Module In a Parallel System Dual Bus System Installation Procedures Shutdown Procedure Complete UPS And Load ShutdownBypass suppl y Input rectifierDB9-DB9 0411533804115339 04116100 15m DB25-DB25LBS cable Parallel board Board LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Specifications Mechanical CharacteristicsElectrical Characteristics Input Rectifier Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical Characteristics Inverter Output Electrical Characteristics Bypass Input MainsElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics System Performance Electrical Characteristics ECO ModeElectrical characteristics system performance Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesLives And Recommended Replacement Time Of Key Components Lifves and recommended replacement time of key componentsReplacing Fuses Key components Life expectancyAppendix 1 Transportation Restraints Removing Procedures 螺Screw钉 Amplified viewM10螺bolt栓 M12螺bolt栓 Restraint300kVA UPS Transportation Restraints Removing Procedures Output 输出变压器 transformer Phase-shifting aAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer