Chapter 4 Operator Control And Display Panel | 27 |
Chapter 4 Operator Control And Display Panel
This chapter expounds the functions and use of the components on the operator control and display panel of the HIPULSE U UPS, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and UPS alarm message list
4.1 Introduction
The operator control and display panel is located on the front door of the UPS. The panel is the access point for operator control and monitoring of all measured parameters, UPS and battery status and of event and alarm logs.
The operator control and display panel is divided into three functional areas: mimic power flow chart, graphic LCD monitor with menu keys, control buttons, as shown in Figure
| Graphic LCD monitor |
|
Mimic power flow chart | with menu keys | Control buttons |
Bypass LED Inverter LED
Rectifier LED
Load LED
Battery LED
HIPULSE U |
| 12:30:36 | ||
|
| Unit #1 | Normal | |
Main |
| Bypass | Output | |
| A(AB) | B(BC) | C(CA) | |
Vphase V | 220 |
| 220 | 220 |
Iphase A | 20.5 |
| 20.5 | 20.5 |
Freq. Hz | 50.1 |
| 50.1 | 50.1 |
Vline V | 380 |
| 380 | 380 |
P. F. | 0.99 |
| 0.99 | 0.99 |
Input Breaker Closed |
| |||
Manual Turn On |
|
| ||
UPS in Normal Mode |
|
?
INVERTER INVERTER
ON OFF
Buzzer
F1 | F2 | F3 | F4 HELP | FAULT | SILENCE |
|
|
|
| CLEAR | ON/OFF |
Alarm LED | LCD menu keys |
|
| ||
|
|
| |||
Figure |
|
|
4.1.1 LED Indicators
The six LEDs mounted on the mimic flow chart represent the various power paths of the UPS, and indicate the current UPS operational status and alarm status by color (red, green, yellow) and state (ON, OFF, flashing), as described in Table
| LED |
| State |
|
|
| Steady green |
| Rectifier LED |
| Flashing green |
|
| Steady red | |
|
|
| |
|
|
| OFF |
|
|
| Steady green |
| Bypass LED |
| Steady red |
|
|
| OFF |
|
|
| Steady green |
| Battery LED |
| Flashing green |
|
| Steady red | |
|
|
| |
|
|
| OFF |
|
|
| Steady green |
| Inverter LED |
| Flashing green |
|
| Steady red | |
|
|
| |
|
|
| OFF |
Table 4-1 Description of LED indicators
Description
Rectifier in normal operation
Input AC normal, but rectifier not operating Rectifier f failed
Rectifier not operating, input ac not available or out of normal range Load on bypass power
Bypass not available, out of normal range or static bypass switch fault Bypass normal, load not on bypass power
Battery normal, but discharging and powering the load Battery
Battery abnormal (failed, absent or polarity reversed) or battery circuit breaker abnormal Battery and battery circuit breaker normal, battery charging
Inverter normal and powering the load
Inverter ON, starting up, synchronizing, or standing by (ECO mode) Inverter failed
Inverter not operating
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual