Emerson U/300/S/12P, 200 Operation Mode, UPS Power Switch Configuration, Battery Circuit Breaker

Page 14

4

Chapter 1 General Description

Operating procedures in ECO mode are the same as those described in Chapter 5 Operating Instructions, except that the load is normally on the bypass mains, the Inverter LED is normally off, and the corresponding alarm message Bypass mode will appear on the LCD.

Warning

In ECO mode the load is not protected against mains distortion.

1.2.5 UPS Power Switch Configuration

Figure 1-2 illustrates the HIPULSE U UPS module in what is known as the split bypass configuration. In the split bypass configuration, the static bypass line is connected by a separate power switch to a dedicated bypass power source which also feeds the maintenance bypass line. Where a separate power source is not available the bypass (Q2) and rectifier (Q1) input supply connections would be linked together.

With the exception of the maintenance bypass switch, all the switches shown must be closed during normal UPS operation.

1.2.6 Battery Circuit Breaker

The battery should be connected to the DC busbar through a circuit breaker fitted inside the battery cabinet — or located adjacent to the batteries where a battery cabinet is not used. This circuit breaker is closed manually, but it contains an undervoltage release coil which enables it to be tripped from the UPS control electronics following certain detected faults. It also has a magnetic trip facility for overload protection.

1.2.7 Battery Temperature Compensation

HIPULSE U UPS system offers a battery temperature compensation circuit. As the temperature inside the battery cabinet/area rises, the DC busbar voltage reduces in order to sustain the battery at its optimum charge voltage. This must be used in conjunction with the battery temperature sensing device.

1.2.8 System Expansion

If necessary, a single module system can be expanded to cater for an increased load requirement by adding additional modules — up to a maximum of six UPS modules can be connected in parallel.

System expansion requires a change in the SETUP of the operator control and display panel of each UPS module. Note:

1.System expansion should be carried out only by trained service personal.

2.The individual modules connected to the system must be of the same power rating.

1.3Operation Mode

The UPS permits operation in the following alternative modes:

Normal mode

The UPS inverter continuously supplies the critical AC load. The rectifier/charger derives power from the AC mains input source and supplies DC power to the inverter while simultaneously float or boost charging its associated backup battery.

Battery mode

Upon failure of the AC mains input power, the critical AC load is supplied by the inverter, which obtains power from the battery. There is no interruption in power to the critical load upon failure or restoration of the AC mains input power after which the Normal mode operation will continue without the necessity of user intervention.

Note: Battery start device (optional) is available for switching the UPS on into Battery (charged) mode directly during mains failure.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 14
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Design Concept FeaturesGeneral Description Hipulse U Module DesignNormal operation Bypass SuppliesSystem Control Philosophy Mains failureECO Mode For Single UPS Only Battery Circuit Breaker Operation ModeUPS Power Switch Configuration Battery Temperature CompensationMaintenance mode Auto-restart modeBypass mode Source Share modeUPS Location Mechanical InstallationEnvironmental Considerations Mechanical Considerations 1905 Front view Air inlet Installation DrawingsPreliminary Checks Top view Air651 761 800 843 Top view Air outlet615 556 1061 1210 1251 Side view Front view 1903 Air1641 Back view Top view Air outlet415 556 1451 1600 1641 Top view Air outlet 1685 1626 Cable access Base view104 424 155 Grille 2 pcs Front正view视图Removable Removable Grille 2 pcsAir inlet 进风口 Ventilation after being installedFront view 正视图 Grille System Configuration Electrical InstallationPower Cabling Cable RatingCable Connections Safety EarthGeneral Notes Protective DevicesNm M10 bolts. Ensure Correct Phase Rotation Cabling ProcedureUPS battery Output of the systemConnections Auxiliary Terminal blockRectifier Bypass Earth Distance From Floor To Connection Point Distance from floor to connection pointDry contact input ports Control CablingMonitoring Board Ports CardDescription of maintenance bypass cabinet port Dry contact output portCommunication ports Auxiliary DC power output portEPO input port Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesW45 Connecting Signal CablesPort side cabinet Cable No. main cabinet W41-5ULW36CSA8 Operator Control And Display Panel LED IndicatorsDescription of LED indicators IntroductionLCD And Menu Keys BuzzerControl Buttons Menu window and UPS data window Detailed Description Of Menu ItemsSystem information window Use the Shift key F1 and up and down arrow keys F2, F3 to Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Previously setBattery capacity test More Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times OK or FaultStart Screen LCD Screen TypesEPO Button Current record windowHelp Screen Default ScreenPrimary Screen Prompt Window UPS Alarm Message List Ongoing update of inverter firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of monitor firmwareIs found to be in error Can also leads to the alarmUnit over load timeout Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesLED status Start-Up Procedure Into Normal ModeStart-Up Procedure Into ECO Mode Battery test type and preconditions Battery Test Mode ProceduresSystem Test Procedure Test procedureLoad equipment is not protected from AC supply aberration Maintenance Bypass Procedure And UPS Shut DownShutdown Procedure Complete UPS And Load Shutdown EPO Procedure UPS Reset ProcedureChanging The Current Date And Time Auto RestartLanguage Selection UPS Batteries BatterySafety Temperature Considerations Installation Design ConsiderationsBattery Installation And Maintenance Battery PopulationBattery Installation Battery ProtectionBattery Connection Connecting The Battery738 BCB Box Optional455 654 1042Ф13 Knockout Battery Temperature Sensor Optional660 General 1+N System Installation Procedures+N System Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesInsertion Procedure Of One Module In a Parallel System Start-Up Procedure Into Normal ModeMaintenance Bypass Procedure And UPS Shut Down Bypass suppl y Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Input rectifier04115339 DB9-DB904115338 04116100 15m DB25-DB25Parallel cable UPS unit UPS parallel system LBS cableParallel board Board LBS cable Parallel并机board板Electrical Characteristics Input Rectifier SpecificationsMechanical Characteristics Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical characteristics inverter output Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics bypass input mainsElectrical characteristics system performance Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesReplacing Fuses Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Key components Life expectancyM10螺bolt栓 M12螺bolt栓 Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view RestraintAmplifiedA处放大图view 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer