Chapter 7 “1+N” System | 55 |
8.Check that no warning message is displayed in the top right corner of the LCD screen and the status of the LEDs as follows:
Table | LED status | |
|
|
|
LED |
| Status |
Rectifier LED |
| Steady green |
Bypass LED |
| Off |
Battery LED |
| Off |
Inverter LED |
| Steady green |
Load LED |
| Steady green |
Alarm LED |
| Off |
7.3.5 Shutdown Procedure (Complete UPS And Load Shutdown)
Refer to 5.7 Shutdown Procedure (Complete UPS And Load Shutdown).
7.4 Dual Bus System Installation Procedures
7.4.1 Cabinet Installation
As shown in Figure
The objective of the dual bus system is to keep the output of two independent UPS systems (or parallel systems) in synchronization using optional load bus synchronization (LBS) cable. One system is designated as the master; the other is designated as the slave. The operating modes covered comprise master and or slave operating inverter or bypass mode.
In installation, place the UPS modules side by side and interconnect as described in the following sections.
Bypass supply | Bypass supply |
Input rectifier
Input rectifier
Input rectifier | Input rectifier |
|
Parallel
cable
LBS
cable
Parallel |
cable |
Load
Figure 7-3 Typical dual bus system (using STS and LBS cable)
7.4.2 Protective Devices
Refer to 3.1.6 Protective Devices.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual