35

4.4 UPS Alarm Message List

Table 4-8 provides the complete list of UPS alarm messages supported for display either on the Records menu (historical data) or in the current record window (prevailing data) as described in 4.1.5 Detailed Description Of Menu Items.

 

 

 

Table 4-8 UPS alarm message list

 

 

 

 

 

Alarm message

 

Description

 

Rectifier comm. fail

Internal RS485 communication failure between monitor and rectifier

 

Mains volt. abnormal

 

Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input

 

 

line-to-neutral voltage amplitude of rectifier

 

 

 

 

Mains undervoltage

Mains voltage is undervoltage. Check the input line voltage

 

Mains freq. abnormal

 

Mains frequency is out of limit range and results in rectifier shutdown. Check the input voltage and

 

 

frequency

 

 

 

 

 

 

 

 

Battery fuse fail

 

Battery fuse flowout led to BCB tripping

 

Rectifier block

Rectifier detected faulty. Rectifier shuts down. Battery discharges

 

Rectifier overtemp.

 

The temperature of heat sink is too high to keep the rectifier running. The UPS can recover

 

 

automatically. Check the environment and ventilation

 

 

 

 

 

 

 

 

Input fuse fail

 

Input fuse blowout led to rectifier turning off

 

Control power 1 fail

UPS operates but Control Power is not available

 

Control power 2 fail

UPS operates but Redundant Control Power is not available

 

Mains phase reversed

Rectifier AC input phase sequence is reversed

 

Rectifier current limit

Rectifier overcurrent led to power limiting operating

 

Soft start fail

 

Rectifier could not start due to low DC bus voltage

 

Input filter fault

 

Filter inductor overtemperature led to filter contactor tripping

 

Filter contactor fault

Filter contactor operation abnormal

 

Filter overcurrent

 

Mains power outside the normal voltage or frequency range of the input passive filter results in filter

 

 

overcurrent. Please find out the reason for the mains power abnormality

 

 

 

 

 

 

 

REC drive cirtuit fault

Rectifier being off due to improper connection of rectifier drive cable or rectifier type setting error

 

REC input Ph. missing

Rectifier input phase missing. Check the input power connection or if the mains power is abnormal

 

DC bus over voltage

 

Rectifier and inverter were shut down because DC bus voltage is too high. Check whether there is a

 

 

fault in rectifier side

 

 

 

 

 

 

 

 

Bus capacitor overvolt

 

Bus capacitor voltage exceeds 350V, rectifier is off. Check the voltages of the two groups of bus

 

 

capacitors

 

 

 

 

 

 

 

 

EPO

 

Emergency Power Off direct access key pressed or external command received

 

Input disconnect open

Rectifier input switch open

 

Input disconnect closed

Rectifier input switch closed

 

Normal mode

Load supplied from inverter output through double conversion of the AC mains input supply

 

Source share mode

 

Load supplied from inverter output through shared double conversion of the AC mains input supply

 

 

and of the Battery supply

 

 

 

 

 

 

 

PPF online

Reactive input filter connected

 

PPF disconnecting

Reactive input filter disconnected

 

Battery mode

 

Load supplied from inverter output through battery

 

No battery

 

Check the battery and the battery wiring; check whether the BCB is closed and the BCB dry contact

 

 

is connected

 

 

 

 

 

 

 

 

Auto start

 

After UPS was shutdown at EOD, inverter auto starts when utility restore

 

Generator connected

 

The generator has been connected to the UPS

 

BCB open

 

Battery Circuit Breaker status (open)

 

BCB closed

 

Battery Circuit Breaker status (closed)

 

Battery float charging

 

Battery status (Float charge mode)

 

Battery boost charging

Battery status (Boost charge mode)

 

Battery discharging

 

Battery status (discharge mode)

 

Battery period testing

 

Automatic periodic battery maintenance discharge test (20% capacity discharge)

 

Batt. capacity testing

 

User initiated battery capacity discharge test (100% capacity discharge)

 

Batt. maint. testing

 

User initiated maintenance discharge test (20% capacity discharge)

 

UPS system testing

 

User initiated system test

 

Inverter in setting

 

Inverter starting up and synchronizing

 

Rectifier in setting

Rectifier starting up and synchronizing

 

Battery Room Alarm

 

Environment in Battery Room Needs Attention

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 45
Contents 31011661 Version V1.0 Revision date April 29Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page General Description FeaturesDesign Concept Hipulse U Module DesignSystem Control Philosophy Bypass SuppliesNormal operation Mains failureECO Mode For Single UPS Only UPS Power Switch Configuration Operation ModeBattery Circuit Breaker Battery Temperature CompensationBypass mode Auto-restart modeMaintenance mode Source Share modeMechanical Installation Environmental ConsiderationsUPS Location Mechanical Considerations Preliminary Checks Installation Drawings1905 Front view Air inlet Top view AirTop view Air outlet 615 556 1061 1210 1251651 761 800 843 1641 Front view 1903 AirSide view Back view Top view Air outletTop view Air outlet 1685 1626 Cable access Base view 104 424 155415 556 1451 1600 1641 Removable Front正view视图Grille 2 pcs Removable Grille 2 pcsVentilation after being installed Front view 正视图Air inlet 进风口 Grille Power Cabling Electrical InstallationSystem Configuration Cable RatingGeneral Notes Safety EarthCable Connections Protective DevicesUPS battery Cabling ProcedureNm M10 bolts. Ensure Correct Phase Rotation Output of the systemAuxiliary Terminal block Rectifier Bypass EarthConnections Distance from floor to connection point Distance From Floor To Connection PointMonitoring Board Ports Control CablingDry contact input ports CardDry contact output port Description of maintenance bypass cabinet portEPO input port Auxiliary DC power output portCommunication ports Description of dry contact output portCommunication port resource deployment table Battery ControlConnecting Power Cables Connecting Main Cabinet And Side CabinetPort side cabinet Cable No. main cabinet Connecting Signal CablesW45 W41-5ULW36CSA8 Description of LED indicators LED IndicatorsOperator Control And Display Panel IntroductionBuzzer Control ButtonsLCD And Menu Keys Detailed Description Of Menu Items System information windowMenu window and UPS data window 中文/English Press the Enter key F4 Adjusts the graphic LCD monitor contrast for best viewingUse the Shift key F1 and up and down arrow keys F2, F3 to Previously setCommunication mode RS232 Reserved Callback times Explanation This setting applies to RS485 communicationBattery capacity test More OK or FaultEPO Button LCD Screen TypesStart Screen Current record windowDefault Screen Primary ScreenHelp Screen Prompt Window UPS Alarm Message List Ongoing update of rectifier firmware Alarm message DescriptionOngoing update of inverter firmware Ongoing update of monitor firmwareUnit over load timeout Can also leads to the alarmIs found to be in error Inverter overtempTo this Operating Instructions Power SwitchesService, cannot be used for other purposes Service socket Designed for use in UPSStart-Up Procedure Into Normal Mode Start-Up Procedure Into ECO ModeLED status System Test Procedure Battery Test Mode ProceduresBattery test type and preconditions Test procedureMaintenance Bypass Procedure And UPS Shut Down Shutdown Procedure Complete UPS And Load ShutdownLoad equipment is not protected from AC supply aberration UPS Reset Procedure EPO ProcedureAuto Restart Language SelectionChanging The Current Date And Time Battery SafetyUPS Batteries Battery Installation And Maintenance Installation Design ConsiderationsTemperature Considerations Battery PopulationBattery Connection Battery ProtectionBattery Installation Connecting The Battery455 BCB Box Optional738 654 1042Battery Temperature Sensor Optional 660Ф13 Knockout +N System 1+N System Installation ProceduresGeneral Preliminary ChecksPower Cables Cabinet InstallationControl Cables 1+N System Operating InstructionsStart-Up Procedure Into Normal Mode Maintenance Bypass Procedure And UPS Shut DownInsertion Procedure Of One Module In a Parallel System Shutdown Procedure Complete UPS And Load Shutdown Dual Bus System Installation ProceduresBypass suppl y Input rectifier04115338 DB9-DB904115339 04116100 15m DB25-DB25Parallel board Board LBS cable LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Mechanical Characteristics SpecificationsElectrical Characteristics Input Rectifier Conformity And StandardElectrical characteristics DC intermediate circuit Electrical Characteristics DC Intermediate CircuitElectrical Characteristics Bypass Input Mains Electrical Characteristics Inverter OutputElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics ECO Mode Electrical Characteristics System PerformanceElectrical characteristics system performance Electrical characteristics ECO modeUPS Key Components And Their Lives Service & MaintenanceLifves and recommended replacement time of key components Lives And Recommended Replacement Time Of Key ComponentsReplacing Fuses Key components Life expectancy螺Screw钉 Amplified view Appendix 1 Transportation Restraints Removing ProceduresM10螺bolt栓 M12螺bolt栓 RestraintOutput 输出变压器 transformer Phase-shifting a 300kVA UPS Transportation Restraints Removing ProceduresAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerOpen the front door RemoveOpen thebackdoorpanel Phase 移相-shifting 变压 器Installation hole covers 400kVA UPS Transportation Restraints Removing ProceduresBolt 2 pcs Transportation restraint Bolt Phase-shiftingPhase-shifting transformer