Emerson 160, 200 Explanation This setting applies to RS485 communication, Communication address

Page 41

 

 

 

 

 

 

 

 

Chapter 4 Operator Control And Display Panel

31

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

Menu

 

Item

 

Explanation

 

 

 

 

 

 

 

 

 

 

This setting applies to RS485 communication and the

 

 

 

 

 

 

 

 

 

 

“one-to-multiple points” communication mode of parallel system. It is

 

 

 

 

 

 

Communication address

 

required to set the parameter Host communication mode of COM1 in

 

 

 

 

 

 

 

 

parallel system to Multipoint to point using background software

 

 

 

 

 

 

 

 

 

 

before setting the communication address of each UPS module

 

 

 

 

 

 

 

 

 

 

Reserved modem function. No need to change the default setting

 

 

 

 

 

 

 

 

Communication mode

 

 

 

 

 

 

 

 

 

 

“RS232”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(reserved)

 

 

 

 

 

 

 

 

Callback times

 

 

 

9

 

 

Settings

 

Phone No.1

(reserved)

 

 

 

 

 

Phone No.2

(reserved)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phone No.3

(reserved)

 

 

 

 

 

 

 

 

 

 

Modifies password for the Command menu.

 

 

 

 

 

 

 

 

 

 

Use the Shift key (F1) to highligt Command Password, press the

 

 

 

 

 

 

 

 

 

 

Enter key (F4).

 

 

 

 

 

 

 

 

Command password

 

Enter each old password digit with up arrow (F2) and use right arrow

 

 

 

 

 

 

 

 

(F3) to access next field. Press the Enter key (F4) when all digits

 

 

 

 

 

 

 

 

 

 

have been entered.

 

 

 

 

 

 

 

 

 

 

Follow prompts and repeat the process for new password

 

 

 

 

 

 

 

 

 

 

Manually initiates battery maintenance test, which will lead to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery being partly discharged, for rough assessment of the battery

 

 

 

 

 

 

 

 

capacity.

 

 

 

 

 

 

 

 

 

 

The Load must exceed 20% and be less than 80% of rated UPS

 

 

 

 

 

 

 

 

 

 

capacity, and the battery must have been float charging for 5 hours or

 

 

 

 

 

 

Battery maintenance test

 

more.

 

 

 

 

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

 

 

 

highligt the desired test. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

Enter each password digit with up arrow (F2) and use right arrow (F3)

 

 

 

 

 

 

 

 

to access next field. Press the Enter key (F4) when all digits have

 

 

 

 

 

 

 

 

 

 

been entered

 

 

 

 

 

 

 

 

 

 

Manually initiates battery capacity test, which will lead to the battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

being completely discharged, for accurate assessment of the battery

 

 

 

 

 

 

 

 

capacity.

 

 

 

 

 

 

 

 

 

 

The Load must exceed 20% and be less than 80% of rated UPS

 

 

 

 

 

 

 

 

 

 

capacity, and the battery must have been float charging for 5 hours or

 

 

 

 

 

 

Battery capacity test

 

more.

 

 

10

 

 

Command*

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

highligt the desired test. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter each password digit with up arrow (F2) and use right arrow (F3)

 

 

 

 

 

 

 

 

to access next field. Press the Enter key (F4) when all digits have

 

 

 

 

 

 

 

 

 

 

been entered

 

 

 

 

 

 

 

 

 

 

Manually initiates the system test.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System test

 

The user actives this function, after 5 seconds, a pop window will

 

 

 

 

 

 

 

 

 

appear to show the result of this diagnosis: Rectifier, Inverter, Monitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK or Fault

 

 

 

 

 

 

 

 

 

 

Manually stop the test, including maintenance test, capacity test and

 

 

 

 

 

 

Stop testing

 

 

 

 

 

 

 

 

system test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manually initiates freshening charge, when the battery is not in boost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

charge state.

 

 

 

 

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

 

Freshening charge

 

highlight this item. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

Enter each password digit with up arrow (F2) and use right arrow (F3)

 

 

 

 

 

 

 

 

to access next field. Press the Enter key (F4) when all digits have

 

 

 

 

 

 

 

 

 

 

been entered

 

 

 

 

 

 

 

 

 

Manually stop the freshening charge

 

 

 

 

 

 

 

 

Stop freshening charge

 

 

 

 

 

 

 

 

Monitor VersionVxxx

 

Displays UPS firmware versions, including inverter, rectifier,

 

 

 

 

 

 

 

 

Rectifier VersionVxxx

 

 

 

11

 

 

Version

 

 

monitoring board firmware versions

 

 

 

 

 

Inverter VersionVxxx

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Displays UPS model information; for example, 380V-50Hz

 

 

 

 

 

 

 

 

UPS model

 

 

Note*: password controlled. The default passward is “12345”, please enter Settings=>Command password to change the password. In case the password is lost, please contact the local customer service center of Emerson

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 41
Contents 31011661 Version V1.0 Revision date April 29Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page General Description FeaturesDesign Concept Hipulse U Module DesignSystem Control Philosophy Bypass SuppliesNormal operation Mains failureECO Mode For Single UPS Only UPS Power Switch Configuration Operation ModeBattery Circuit Breaker Battery Temperature CompensationBypass mode Auto-restart modeMaintenance mode Source Share modeUPS Location Mechanical InstallationEnvironmental Considerations Mechanical Considerations Preliminary Checks Installation Drawings1905 Front view Air inlet Top view Air651 761 800 843 Top view Air outlet615 556 1061 1210 1251 1641 Front view 1903 AirSide view Back view Top view Air outlet415 556 1451 1600 1641 Top view Air outlet 1685 1626 Cable access Base view104 424 155 Removable Front正view视图Grille 2 pcs Removable Grille 2 pcsAir inlet 进风口 Ventilation after being installedFront view 正视图 Grille Power Cabling Electrical InstallationSystem Configuration Cable RatingGeneral Notes Safety EarthCable Connections Protective DevicesUPS battery Cabling ProcedureNm M10 bolts. Ensure Correct Phase Rotation Output of the systemConnections Auxiliary Terminal blockRectifier Bypass Earth Distance from floor to connection point Distance From Floor To Connection PointMonitoring Board Ports Control CablingDry contact input ports CardDry contact output port Description of maintenance bypass cabinet portEPO input port Auxiliary DC power output portCommunication ports Description of dry contact output portCommunication port resource deployment table Battery ControlConnecting Power Cables Connecting Main Cabinet And Side CabinetPort side cabinet Cable No. main cabinet Connecting Signal CablesW45 W41-5ULW36CSA8 Description of LED indicators LED IndicatorsOperator Control And Display Panel IntroductionLCD And Menu Keys BuzzerControl Buttons Menu window and UPS data window Detailed Description Of Menu ItemsSystem information window 中文/English Press the Enter key F4 Adjusts the graphic LCD monitor contrast for best viewingUse the Shift key F1 and up and down arrow keys F2, F3 to Previously setCommunication mode RS232 Reserved Callback times Explanation This setting applies to RS485 communicationBattery capacity test More OK or FaultEPO Button LCD Screen TypesStart Screen Current record windowHelp Screen Default ScreenPrimary Screen Prompt Window UPS Alarm Message List Ongoing update of rectifier firmware Alarm message DescriptionOngoing update of inverter firmware Ongoing update of monitor firmwareUnit over load timeout Can also leads to the alarmIs found to be in error Inverter overtempTo this Operating Instructions Power SwitchesService, cannot be used for other purposes Service socket Designed for use in UPSLED status Start-Up Procedure Into Normal ModeStart-Up Procedure Into ECO Mode System Test Procedure Battery Test Mode ProceduresBattery test type and preconditions Test procedureLoad equipment is not protected from AC supply aberration Maintenance Bypass Procedure And UPS Shut DownShutdown Procedure Complete UPS And Load Shutdown UPS Reset Procedure EPO ProcedureChanging The Current Date And Time Auto RestartLanguage Selection UPS Batteries BatterySafety Battery Installation And Maintenance Installation Design ConsiderationsTemperature Considerations Battery PopulationBattery Connection Battery ProtectionBattery Installation Connecting The Battery455 BCB Box Optional738 654 1042Ф13 Knockout Battery Temperature Sensor Optional660 +N System 1+N System Installation ProceduresGeneral Preliminary ChecksPower Cables Cabinet InstallationControl Cables 1+N System Operating InstructionsInsertion Procedure Of One Module In a Parallel System Start-Up Procedure Into Normal ModeMaintenance Bypass Procedure And UPS Shut Down Shutdown Procedure Complete UPS And Load Shutdown Dual Bus System Installation ProceduresBypass suppl y Input rectifier04115338 DB9-DB904115339 04116100 15m DB25-DB25Parallel board Board LBS cable LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Mechanical Characteristics SpecificationsElectrical Characteristics Input Rectifier Conformity And StandardElectrical characteristics DC intermediate circuit Electrical Characteristics DC Intermediate CircuitElectrical Characteristics Bypass Input Mains Electrical Characteristics Inverter OutputElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics ECO Mode Electrical Characteristics System PerformanceElectrical characteristics system performance Electrical characteristics ECO modeUPS Key Components And Their Lives Service & MaintenanceLifves and recommended replacement time of key components Lives And Recommended Replacement Time Of Key ComponentsReplacing Fuses Key components Life expectancy螺Screw钉 Amplified view Appendix 1 Transportation Restraints Removing ProceduresM10螺bolt栓 M12螺bolt栓 RestraintOutput 输出变压器 transformer Phase-shifting a 300kVA UPS Transportation Restraints Removing ProceduresAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerOpen the front door RemoveOpen thebackdoorpanel Phase 移相-shifting 变压 器Installation hole covers 400kVA UPS Transportation Restraints Removing ProceduresBolt 2 pcs Transportation restraint Bolt Phase-shiftingPhase-shifting transformer