34 | Chapter 4 Operator Control And Display Panel |
Help information
Select the current record window
Select the previous menu item
Select the next menu item
Q3
Q2
Q1
Q5
|
|
|
| ? |
F1 | F2 | F3 | F4 | HELP |
| Figure | Help screen |
|
Operation of the HELP key:
1.Only at the primary screen can you use the HELP key to display the help screen.
2.The HELP key is invalid at the start screen.
3.At the default screen, help screen, or when the LCD backlight is off, the primary screen will return if you press the HELP key.
4.3Prompt Window
A prompt window is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command. The prompts are provided in Table
| Table | ||
|
|
| |
No. | Prompt | Meaning | |
1 | Transfer with interrupt, confirm or | Inverter and Bypass supplies are not synchronized and any load transfer | |
cancel | between the supplies will cause a brief load interruption | ||
| |||
|
|
| |
2 | The load is too high to be | The total load must be less than the capacity of one unit to allow a parallel | |
transferred with interrupt | system to perform an interrupted transfer from bypass to inverter | ||
| |||
|
|
| |
3 | This operation leads to output | No alternative supply is available and any Inverter Off operation will cause the | |
shutdown, confirm or cancel | load to be | ||
| |||
|
|
| |
4 | This operation leads to inverter | Turning off this inverter will lead to the overload of remaining inverter(s) in a | |
overload, confirm or cancel | parallel system | ||
| |||
|
|
| |
5 | Turn on more UPS to carry current | The number of paralleled inverters already turned on is insufficient to carry the | |
load | existing load | ||
| |||
|
|
| |
| Battery will be depleted, confirm or | Battery capacity test discharges the battery 100%. This prompt apears to | |
6 | require your confirmation. Cancelling the test will ends the test and transfers the | ||
cancel | |||
| UPS to Normal mode | ||
|
| ||
|
|
| |
7 | System selftest finished, everything | No action required | |
is ok | |||
|
| ||
|
|
| |
8 | System selftest finished, please | Check the current record window | |
check the current warnings | |||
|
| ||
|
|
| |
9 | Enter control password | Required for battery or UPS test (default: 12345) | |
| Battery selftest condition is low, | Battery test condition is not met. Please check whether the battery is in boost | |
10 | please check battery state and | charge state and the load level meet the battery test conditions. To initiate the | |
| loadlevel | battery test, the load must range between 20% and 80% | |
|
|
| |
| Freshening charge condition is low, | This prompt appears when you select the freshening charge command while | |
11 | please check battery settings and | ||
the freshening charge condition is not met (such as no battery, charger failure) | |||
| state | ||
|
| ||
|
|
|
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual