Appendix 1 Transportation Restraints Removing Procedures

65

5.Reinstall the installation hole cover and the lower switch baffle plate with the screws removed in step 1. You might as well install the lower switch baffle plate after UPS commissioning.

6.Reinstall the back panel of the cabinet with the screws removed in step 2. You can also carry out this step after UPS commissioning.

Transformer transportation restraints removing procedures for UPS with 12-pulse rectifier

1.Repeat the preceding steps 1 through 4 to remove the transportation restraints of the output transformer (see Figure 3).

Output 变压transformer

Phase-shifting A

移相变压A transformer

M10bolt

M12bolt

Transportation固定件 restraint

A amplifiedA放大view

Figure 3 Removing the transformer transportation restraints

2. Remove the transportation restraints of the phase-shifting transformer.

There are two transportation restraints respectively in the front and at the back, totally four, at the bottom of the phase-shifting transformer. Remove the two M10 bots at both sides and one M12 bolt in the middle of each transportation restraint, as shown in Figure 3. Remove the four transportation restraints, and then reinstall the four M12 bolts in their original positions.

3.Repeat the preceding steps 5 and 6.

2.300kVA UPS Transportation Restraints Removing Procedures

Transformer transportation restraints removing procedures for UPS with 6-pulse rectifier

1. Remove the back panel of the cabinet to reveal the output transformer, as shown in Figure 4. Retain the screws.

M10bolts螺栓

Output 变压transformer

Transportation固定件 restraint

A放大

A amplified view

A

Figure 4 Removing the output transformer transportation restraints

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 75
Contents 31011661 Version V1.0 Revision date April 29Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Hipulse U Module Design FeaturesGeneral Description Design ConceptMains failure Bypass SuppliesSystem Control Philosophy Normal operationECO Mode For Single UPS Only Battery Temperature Compensation Operation ModeUPS Power Switch Configuration Battery Circuit BreakerSource Share mode Auto-restart modeBypass mode Maintenance modeMechanical Installation Environmental ConsiderationsUPS Location Mechanical Considerations Top view Air Installation DrawingsPreliminary Checks 1905 Front view Air inletTop view Air outlet 615 556 1061 1210 1251651 761 800 843 Back view Top view Air outlet Front view 1903 Air1641 Side viewTop view Air outlet 1685 1626 Cable access Base view 104 424 155415 556 1451 1600 1641 Removable Grille 2 pcs Front正view视图Removable Grille 2 pcsVentilation after being installed Front view 正视图Air inlet 进风口 Grille Cable Rating Electrical InstallationPower Cabling System ConfigurationProtective Devices Safety EarthGeneral Notes Cable ConnectionsOutput of the system Cabling ProcedureUPS battery Nm M10 bolts. Ensure Correct Phase RotationAuxiliary Terminal block Rectifier Bypass EarthConnections Distance from floor to connection point Distance From Floor To Connection PointCard Control CablingMonitoring Board Ports Dry contact input portsDry contact output port Description of maintenance bypass cabinet portDescription of dry contact output port Auxiliary DC power output portEPO input port Communication portsCommunication port resource deployment table Battery ControlConnecting Power Cables Connecting Main Cabinet And Side CabinetW41-5 Connecting Signal CablesPort side cabinet Cable No. main cabinet W45ULW36CSA8 Introduction LED IndicatorsDescription of LED indicators Operator Control And Display PanelBuzzer Control ButtonsLCD And Menu Keys Detailed Description Of Menu Items System information windowMenu window and UPS data window Previously set Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Use the Shift key F1 and up and down arrow keys F2, F3 toOK or Fault Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times Battery capacity test MoreCurrent record window LCD Screen TypesEPO Button Start ScreenDefault Screen Primary ScreenHelp Screen Prompt Window UPS Alarm Message List Ongoing update of monitor firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of inverter firmwareInverter overtemp Can also leads to the alarmUnit over load timeout Is found to be in errorTo this Operating Instructions Power SwitchesService, cannot be used for other purposes Service socket Designed for use in UPSStart-Up Procedure Into Normal Mode Start-Up Procedure Into ECO ModeLED status Test procedure Battery Test Mode ProceduresSystem Test Procedure Battery test type and preconditionsMaintenance Bypass Procedure And UPS Shut Down Shutdown Procedure Complete UPS And Load ShutdownLoad equipment is not protected from AC supply aberration UPS Reset Procedure EPO ProcedureAuto Restart Language SelectionChanging The Current Date And Time Battery SafetyUPS Batteries Battery Population Installation Design ConsiderationsBattery Installation And Maintenance Temperature ConsiderationsConnecting The Battery Battery ProtectionBattery Connection Battery Installation654 1042 BCB Box Optional455 738Battery Temperature Sensor Optional 660Ф13 Knockout Preliminary Checks 1+N System Installation Procedures+N System GeneralPower Cables Cabinet InstallationControl Cables 1+N System Operating InstructionsStart-Up Procedure Into Normal Mode Maintenance Bypass Procedure And UPS Shut DownInsertion Procedure Of One Module In a Parallel System Input rectifier Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Bypass suppl y04116100 15m DB25-DB25 DB9-DB904115338 04115339Parallel并机board板 LBS cableParallel board Board LBS cable Parallel cable UPS unit UPS parallel systemConformity And Standard SpecificationsMechanical Characteristics Electrical Characteristics Input RectifierElectrical characteristics DC intermediate circuit Electrical Characteristics DC Intermediate CircuitElectrical characteristics bypass input mains Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics inverter outputElectrical characteristics ECO mode Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics system performanceUPS Key Components And Their Lives Service & MaintenanceKey components Life expectancy Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Replacing FusesRestraint Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view M10螺bolt栓 M12螺bolt栓M10bolts螺栓 Output 输出变压器 transformer 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a AmplifiedA处放大图viewOpen the front door RemoveOpen thebackdoorpanel Phase 移相-shifting 变压 器Installation hole covers 400kVA UPS Transportation Restraints Removing ProceduresBolt 2 pcs Transportation restraint Bolt Phase-shiftingPhase-shifting transformer