
2 | Chapter 1 General Description |
1.2.2 Bypass Supplies
The circuit block annotated “Static switch” in Figure
Bypass |
|
|
|
|
mains supply | Maintenance bypass switch Q3 | UPS |
| |
| Bypass switch Q2 |
|
|
|
Input mains | Rectifier | Inverter | Static switch |
|
|
|
|
| |
supply | DC bus |
|
|
|
|
|
|
| |
| Input switch Q1 |
| Output switch Q5 | UPS output |
|
|
|
| |
| C.B. |
|
|
|
Battery
Battery circuit breaker
Figure 1-2 UPS power switches configuration
To provide a clean
A manually controlled, maintenance bypass supply is also incorporated into the UPS design. Its purpose is to enable the critical load to be powered from the mains (bypass) supply while the UPS is shut down for routine maintenance.
Note: The load equipment is not protected from normal supply aberrations when operating on bypass side or in the maintenance bypass mode.
1.2.3 System Control Philosophy
Normal operation
During normal operation, that is, when the UPS input supply is present and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical load busbars. The battery circuit breaker (BCB) is also closed and the battery is therefore permanently float charged at the DC busbar voltage level.
(“1+N” parallel UPS system) Note: As the unit outputs are connected in parallel, the system checks that the inverter control circuits are perfectly synchronized with one another and with the bypass mains in terms of both frequency and phase and that they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message appears while synchronization is in progress.
A module's static switch cannot close until these conditions are satisfied.
Mains failure
If the power mains has a failure or is out of tolerance the rectifier will go off automatically, while the inverter will continue to operate on power from the battery for a period of time which depends on the load and the capacity of the battery. If the mains supply has not returned within this time, the inverter will go off automatically and an alarm message will appear on the operator control and display panel of the UPS.
Critical load will not be interrupted in the event of a drop or return of the AC power mains.
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual