| Chapter 8 | Specifications | 59 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| Power rating (kVA) |
|
|
|
|
| ||
| Item |
| Unit | 160 | 160 | 200 | 200 |
| 300 | 300 | 400 |
| 400 |
|
|
|
|
| |||||||||||
| Rated input power 2 |
| kVA | 197 | 191 | 245 | 236 |
| 365 | 354 | 488 |
| 469 |
|
| Rated input current2 |
| A | 298 | 289 | 371 | 358 |
| 551 | 535 | 739 |
| 708 |
|
| Maximal input Power3 |
| kVA | 246 | 239 | 306 | 295 |
| 420 | 407 | 609 |
| 584 |
|
| Maximal input |
| A | 373 | 362 | 464 | 447 |
| 634 | 616 | 931 |
| 885 |
|
| current3 |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Duration of |
|
|
|
|
|
|
|
|
|
|
|
|
|
| progressive power |
| s |
|
|
|
| 5~300 |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note:
1. With mains at
2.
3.
4. Set by dedicated background software
8.5 Electrical Characteristics (DC Intermediate Circuit)
Table 8-5 Electrical characteristics (DC intermediate circuit)
| Item |
| Unit |
| Power rating (kVA) |
| ||
|
| 160 | 200 |
| 300 | 400 | ||
|
|
|
|
| ||||
| Voltage range for inverter operation |
| Vdc |
|
| 320~490 |
| |
| Recommended number of |
|
|
| 192 (380Vac) |
| ||
|
| pcs |
| 198 (400Vac) |
| |||
|
|
|
|
| 204 (415Vac) |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| 432 (380Vac) |
| ||
| Recommended float charge voltage 2.25V/el.1 |
| Vdc |
| 446 (400Vac) |
| ||
|
|
|
|
| 459 (415Vac) |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| 451 (380Vac) |
| ||
| Recommended boost charge voltage 2.35V/el.1 |
| Vdc |
| 465 (400Vac) |
| ||
|
|
|
|
| 479 (415Vac) |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| 461 (380Vac) |
| ||
| Maximum voltage on manual charge 2.40 V/el.1 |
| Vdc |
| 475 (400Vac) |
| ||
|
|
|
|
| 490 (415Vac) |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| 471 (380Vac) |
| ||
|
| Vdc |
| 485 (400Vac) |
| |||
|
|
|
|
| 500 (415Vac) |
| ||
|
|
|
|
|
|
|
| |
| Max boost charge duration 3 |
| min |
|
| 480~1800 |
| |
| Freshening charge duration3 |
| h |
|
| 1~36 |
| |
|
| A |
| 0.001C~0.025C |
| |||
| Ripple voltage superimposed 4 | % |
|
| ≤1 |
| ||
| Note: |
|
|
|
|
|
|
|
1.(According to rated voltage).
2.Factory set for rated 380V, different cells number and voltage per cell may be set by configuration software.
3.Set by software.
4.Battery disconnected, RMS percentage value referred to DC voltage
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual