Emerson 200, U/300/S/12P, U /400/S/12P, 400KVA 中文/English Press the Enter key F4, Previously set

Page 40

30

Chapter 4

Operator Control And Display Panel

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

Menu

 

Item

 

Explanation

 

 

 

 

 

 

Sout (kVA)

Apparent power

 

 

 

 

 

 

Pout (kW)

 

Active power

 

4

 

 

Load

 

Qout (kVAR)

Reactive power

 

 

 

 

 

 

Loadlevel (%)

 

The percentage of the UPS rating load

 

 

 

 

 

 

Crest factor

 

Output current crest factor

 

 

 

 

 

 

Sout (kVA)

Apparent power

 

 

 

 

 

 

Pout (kW)

 

Active power

 

5

 

 

System

 

Qout (kVAR)

Reactive power

 

 

 

 

 

 

Single system, no parallel data

 

When configured as a single unit, UPS has only native load, no

 

 

 

 

 

 

 

system load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery voltage (V)

 

Battery bus voltage

 

 

 

 

 

 

Battery current (A)

 

Battery bus current

 

 

 

 

 

 

Battery temperature (°C)

Internal battery temperature °C

 

6

 

 

Battery

 

Battery remain time (Min.)

Battery run time remaining

 

 

 

 

 

 

Battery boost charging

Battery is boost charging

 

 

 

 

 

 

Battery float charging

 

Battery is float charging

 

 

 

 

 

 

Battery is not connected

Battery is not connected

 

 

 

 

 

 

……

 

 

 

 

 

 

 

 

Inverter output abnormal

 

 

 

 

 

 

 

20-01-2006 11:30:02

 

Displays up to 512-event history log indicating system status with

 

7

 

 

Records

22-01-2006 13:38:06

 

start/stop date and time stamp for each event.

 

 

 

 

Battery maintained

 

You may scroll through the history log.

 

 

 

 

 

 

 

 

 

 

 

 

22-01-2006 13:38:02

 

Refer to Table 4-8 for a complete list of UPS alarm messages

 

 

 

 

 

22-01-2006 13:38:36

 

 

 

 

 

 

 

 

……

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selects display in Chinese or English.

 

 

 

 

 

 

 

 

Use F1, up and down arrow keys (F2, F3) to select this menu item,

 

8

 

 

Language

 

中文/English

 

and press the Enter key (F4).

 

 

 

 

 

 

 

 

Use left and right arrow keys (F2, F3) to reach desired language and

 

 

 

 

 

 

 

 

press the Enter key (F4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjusts the graphic LCD monitor contrast for best viewing.

 

 

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

Display contrast

 

highligt this setting. Press the Enter key (F4).

 

 

 

 

 

 

 

 

Select setting with left and right arrows (F2, F3) and press the Enter

 

 

 

 

 

 

 

 

key (F4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YYYY MM DD, DD MM YYYY and MM DD YYYY formats can be

 

 

 

 

 

 

 

 

selected.

 

 

 

 

 

 

Date format set

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

highligt this setting. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select setting with left and right arrows (F2, F3) and press the Enter

 

 

 

 

 

 

 

 

key (F4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjusts time (in 24-hr format) and Date format (in user defined format

 

9

 

 

Settings

 

 

 

previously set).

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Date & time

 

highligt this setting. Press the Enter key (F4).

 

 

 

 

 

 

 

 

Enter each date or time digit with up arrow (F2) and use right arrow

 

 

 

 

 

 

 

 

(F3) to access next field. Press the Enter key (F4) when all digits

 

 

 

 

 

 

 

 

have been entered

 

 

 

 

 

 

Comm1 baud rate

 

Adjusts the transmission speed of any of the 3 UPS communication

 

 

 

 

 

 

(Monitoring board RS232-1,

 

 

 

 

 

 

 

 

ports available. Available settings are

 

 

 

 

 

 

Intellislot 2)

 

 

 

 

 

 

 

 

- 9600bps (default setting, SNMP card supports this baud rate only)

 

 

 

 

 

 

Comm2 baud rate

 

 

 

 

 

 

 

 

- 4800bps

 

 

 

 

 

 

(Monitoring board RS232-2,

 

 

 

 

 

 

 

 

- 2400bps

 

 

 

 

 

 

Intellislot 1)

 

 

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

Comm3 baud rate

 

 

 

 

 

 

 

 

highligt the desired port and baud rate. Press the Enter key (F4)

 

 

 

 

 

 

(Monitoring board Intellislot 3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 40
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Features General DescriptionDesign Concept Hipulse U Module DesignBypass Supplies System Control PhilosophyNormal operation Mains failureECO Mode For Single UPS Only Operation Mode UPS Power Switch ConfigurationBattery Circuit Breaker Battery Temperature CompensationAuto-restart mode Bypass modeMaintenance mode Source Share modeEnvironmental Considerations Mechanical InstallationUPS Location Mechanical Considerations Installation Drawings Preliminary Checks1905 Front view Air inlet Top view Air615 556 1061 1210 1251 Top view Air outlet651 761 800 843 Front view 1903 Air 1641Side view Back view Top view Air outlet104 424 155 Top view Air outlet 1685 1626 Cable access Base view415 556 1451 1600 1641 Front正view视图 RemovableGrille 2 pcs Removable Grille 2 pcsFront view 正视图 Ventilation after being installedAir inlet 进风口 Grille Electrical Installation Power CablingSystem Configuration Cable RatingSafety Earth General NotesCable Connections Protective DevicesCabling Procedure UPS batteryNm M10 bolts. Ensure Correct Phase Rotation Output of the systemRectifier Bypass Earth Auxiliary Terminal blockConnections Distance From Floor To Connection Point Distance from floor to connection pointControl Cabling Monitoring Board PortsDry contact input ports CardDescription of maintenance bypass cabinet port Dry contact output portAuxiliary DC power output port EPO input portCommunication ports Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesConnecting Signal Cables Port side cabinet Cable No. main cabinetW45 W41-5ULW36CSA8 LED Indicators Description of LED indicatorsOperator Control And Display Panel IntroductionControl Buttons BuzzerLCD And Menu Keys System information window Detailed Description Of Menu ItemsMenu window and UPS data window Adjusts the graphic LCD monitor contrast for best viewing 中文/English Press the Enter key F4Use the Shift key F1 and up and down arrow keys F2, F3 to Previously setExplanation This setting applies to RS485 communication Communication mode RS232 Reserved Callback timesBattery capacity test More OK or FaultLCD Screen Types EPO ButtonStart Screen Current record windowPrimary Screen Default ScreenHelp Screen Prompt Window UPS Alarm Message List Alarm message Description Ongoing update of rectifier firmwareOngoing update of inverter firmware Ongoing update of monitor firmwareCan also leads to the alarm Unit over load timeoutIs found to be in error Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into ECO Mode Start-Up Procedure Into Normal ModeLED status Battery Test Mode Procedures System Test ProcedureBattery test type and preconditions Test procedureShutdown Procedure Complete UPS And Load Shutdown Maintenance Bypass Procedure And UPS Shut DownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureLanguage Selection Auto RestartChanging The Current Date And Time Safety BatteryUPS Batteries Installation Design Considerations Battery Installation And MaintenanceTemperature Considerations Battery PopulationBattery Protection Battery ConnectionBattery Installation Connecting The BatteryBCB Box Optional 455738 654 1042660 Battery Temperature Sensor OptionalФ13 Knockout 1+N System Installation Procedures +N SystemGeneral Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesMaintenance Bypass Procedure And UPS Shut Down Start-Up Procedure Into Normal ModeInsertion Procedure Of One Module In a Parallel System Dual Bus System Installation Procedures Shutdown Procedure Complete UPS And Load ShutdownBypass suppl y Input rectifierDB9-DB9 0411533804115339 04116100 15m DB25-DB25LBS cable Parallel board Board LBS cableParallel cable UPS unit UPS parallel system Parallel并机board板Specifications Mechanical CharacteristicsElectrical Characteristics Input Rectifier Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical Characteristics Inverter Output Electrical Characteristics Bypass Input MainsElectrical characteristics inverter output Electrical characteristics bypass input mainsElectrical Characteristics System Performance Electrical Characteristics ECO ModeElectrical characteristics system performance Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesLives And Recommended Replacement Time Of Key Components Lifves and recommended replacement time of key componentsReplacing Fuses Key components Life expectancyAppendix 1 Transportation Restraints Removing Procedures 螺Screw钉 Amplified viewM10螺bolt栓 M12螺bolt栓 Restraint300kVA UPS Transportation Restraints Removing Procedures Output 输出变压器 transformer Phase-shifting aAmplifiedA处放大图view M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer