56 Chapter 7 “1+N” System

7.4.3 Power Cables

The wiring of power cables is similar to that of single module system. Refer to 3.1 Power Cabling.

The bypass and the main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be located upstream of the common neutral sinking point.

7.4.4 Control Cables

Control cable connection of dual bus system consisting of two single units

If the dual bus system consists of two single units, use the optional 9-core LBS cable to connect between the LBS interfaces (X4 socket on parallel board) of the two single units, and use another optional LBS cable to connect between any two 25-core interfaces (X2-1 or X2-2) of the two single units, as shown in Figure 7-4.

Warning

Although the dedicated 25-core LBS cable looks like the parallel cable, it is absolutely not the parallel cable, and cannot be replaced by it. Otherwise, UPS system chaos may occur.

 

 

04116319

20m

DB9-DB9

 

 

Parallel board

04115338

10m

DB9-DB9

Parallel board

04115339

15m

DB9-DB9

X4

 

LBS cable

X4

 

X2-1

X2-2

 

 

 

X2-1

X2-2

 

 

LBS cable

 

 

 

 

04116100 15m DB25-DB25

 

 

X1-1

X1-2

 

 

 

X1-1

X1-2

UPS unit 1

UPS unit 2

Figure 7-4 Control cable connection of dual bus system consisting of two single units

Control cable connection of dual bus system consisting of a single unit and a parallel system

Figure 7-5 shows the control cable connection of the dual bus system consisting of a single unit and a parallel system composed of two or more single units. Use the optional 9-core LBS cable to connect from the LBS interface (X4 socket on parallel board) of the single unit to the LBS interface of any single unit in the parallel system; and use another optional LBS cable to connect from any 25-core interface (X2-1 or X2-2) of the single unit to the LBS interface of any single unit except for the aforesaid one in the parallel system, note that this LBS cable has a 9-core end and a 25-core end, respectively connecting the X4 interface of the parallel system and the 25-core interface of the single unit.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Image 66
Contents Version V1.0 Revision date April 29 31011661Page Page Manual Describes The Following Equipment Safety Precautions Page Contents Page Page Page Design Concept FeaturesGeneral Description Hipulse U Module DesignNormal operation Bypass SuppliesSystem Control Philosophy Mains failureECO Mode For Single UPS Only Battery Circuit Breaker Operation ModeUPS Power Switch Configuration Battery Temperature CompensationMaintenance mode Auto-restart modeBypass mode Source Share modeMechanical Installation Environmental ConsiderationsUPS Location Mechanical Considerations 1905 Front view Air inlet Installation DrawingsPreliminary Checks Top view AirTop view Air outlet 615 556 1061 1210 1251651 761 800 843 Side view Front view 1903 Air1641 Back view Top view Air outletTop view Air outlet 1685 1626 Cable access Base view 104 424 155415 556 1451 1600 1641 Grille 2 pcs Front正view视图Removable Removable Grille 2 pcsVentilation after being installed Front view 正视图Air inlet 进风口 Grille System Configuration Electrical InstallationPower Cabling Cable RatingCable Connections Safety EarthGeneral Notes Protective DevicesNm M10 bolts. Ensure Correct Phase Rotation Cabling ProcedureUPS battery Output of the systemAuxiliary Terminal block Rectifier Bypass EarthConnections Distance From Floor To Connection Point Distance from floor to connection pointDry contact input ports Control CablingMonitoring Board Ports CardDescription of maintenance bypass cabinet port Dry contact output portCommunication ports Auxiliary DC power output portEPO input port Description of dry contact output portBattery Control Communication port resource deployment tableConnecting Main Cabinet And Side Cabinet Connecting Power CablesW45 Connecting Signal CablesPort side cabinet Cable No. main cabinet W41-5ULW36CSA8 Operator Control And Display Panel LED IndicatorsDescription of LED indicators IntroductionBuzzer Control ButtonsLCD And Menu Keys Detailed Description Of Menu Items System information windowMenu window and UPS data window Use the Shift key F1 and up and down arrow keys F2, F3 to Adjusts the graphic LCD monitor contrast for best viewing中文/English Press the Enter key F4 Previously setBattery capacity test More Explanation This setting applies to RS485 communicationCommunication mode RS232 Reserved Callback times OK or FaultStart Screen LCD Screen TypesEPO Button Current record windowDefault Screen Primary ScreenHelp Screen Prompt Window UPS Alarm Message List Ongoing update of inverter firmware Alarm message DescriptionOngoing update of rectifier firmware Ongoing update of monitor firmwareIs found to be in error Can also leads to the alarmUnit over load timeout Inverter overtempTo this Power Switches Operating InstructionsService socket Designed for use in UPS Service, cannot be used for other purposesStart-Up Procedure Into Normal Mode Start-Up Procedure Into ECO ModeLED status Battery test type and preconditions Battery Test Mode ProceduresSystem Test Procedure Test procedureMaintenance Bypass Procedure And UPS Shut Down Shutdown Procedure Complete UPS And Load ShutdownLoad equipment is not protected from AC supply aberration EPO Procedure UPS Reset ProcedureAuto Restart Language SelectionChanging The Current Date And Time Battery SafetyUPS Batteries Temperature Considerations Installation Design ConsiderationsBattery Installation And Maintenance Battery PopulationBattery Installation Battery ProtectionBattery Connection Connecting The Battery738 BCB Box Optional455 654 1042Battery Temperature Sensor Optional 660Ф13 Knockout General 1+N System Installation Procedures+N System Preliminary ChecksCabinet Installation Power Cables1+N System Operating Instructions Control CablesStart-Up Procedure Into Normal Mode Maintenance Bypass Procedure And UPS Shut DownInsertion Procedure Of One Module In a Parallel System Bypass suppl y Dual Bus System Installation ProceduresShutdown Procedure Complete UPS And Load Shutdown Input rectifier04115339 DB9-DB904115338 04116100 15m DB25-DB25Parallel cable UPS unit UPS parallel system LBS cableParallel board Board LBS cable Parallel并机board板Electrical Characteristics Input Rectifier SpecificationsMechanical Characteristics Conformity And StandardElectrical Characteristics DC Intermediate Circuit Electrical characteristics DC intermediate circuitElectrical characteristics inverter output Electrical Characteristics Inverter OutputElectrical Characteristics Bypass Input Mains Electrical characteristics bypass input mainsElectrical characteristics system performance Electrical Characteristics System PerformanceElectrical Characteristics ECO Mode Electrical characteristics ECO modeService & Maintenance UPS Key Components And Their LivesReplacing Fuses Lives And Recommended Replacement Time Of Key ComponentsLifves and recommended replacement time of key components Key components Life expectancyM10螺bolt栓 M12螺bolt栓 Appendix 1 Transportation Restraints Removing Procedures螺Screw钉 Amplified view RestraintAmplifiedA处放大图view 300kVA UPS Transportation Restraints Removing ProceduresOutput 输出变压器 transformer Phase-shifting a M10bolts螺栓 Output 输出变压器 transformerPhase 移相-shifting 变压 器 Open the front door RemoveOpen thebackdoorpanel400kVA UPS Transportation Restraints Removing Procedures Installation hole coversTransportation restraint Bolt Phase-shifting Bolt 2 pcsPhase-shifting transformer