APC AP9208, AP9608 manual Configure Call-UPS, Initial Logging On

Page 11

3.5 Configure Call-UPS II

Call-UPSII requires on-site configuration before remote operation. You will be able to change any of the settings later by the remote connection. Follow these steps to configure Call-UPSII for:

Communication parameters

Password protection

Time and date

Paging (optional)

Dial-back security (optional)

Event logging (optional)

Initial Logging On

Connect DTE equipment (a dumb terminal or a computer running termi- nal emulation software) to the Management Port of Call-UPSII using the supplied null modem cable. It may be necessary to use an adapter (not supplied) to connect the DTE equipment to the null modem cable.

Set the communication parameters of the DTE equipment to 9600 bits per second, 8 data bits, no parity, and 1 stop bit (9600, 8, N, 1).

With Call-UPSII running (Status Indicator on steady), press CTRL + P (press and hold the CTRL key while pressing the P key). At the prompt:

Enter Password>

Type in APC and press ENTER.

Note: “ APCis the factory default password for Call-UPS II. If the default has been changed through previous configuration, enter the changed password. Call-UPS II communication is case sensitive. Enter APC in upper case.

On correct entry of the password, Call-UPSII displays the following information:

---------------------- SMART-UPS 700 --------------------

Call-UPS II by American Power Conversion Corp

(c) Copyright 1994,95,97 All Rights Reserved

Site ID: 12345678

Location: Physical Location of This UPS

Press Any Key To Continue...

7

Image 11
Contents Call-UPSII Thank You Contents Problem Resolution Hardware Requirements IntroductionOverview UPS Monitoring Port External Version Product DescriptionCall-UPS II Panel Management PortWith Smart-UPS With Matrix-UPS Power Port External VersionUPS Cable External Version Status LED Indication Status IndicatorReceiving Inspection Installation and SetupInstallation HandlingExternal Version Confirm OperationInitial Logging On Configure Call-UPSPress any key to bring up the Main menu Customize SettingsConnect to Modem SmartSlot Configuration External Configuration Logging On to Call-UPS UPS Status and DiagnosticsOperation With Smart-UPS and Matrix-UPS UPS Status Smart-UPS and Matrix-UPS Description Sleeping Inverter Shutdown UPS Status and Diagnostics Symmetra Power Array Description With Symmetra Power ArrayUPS Status and Diagnostics Page RIM Page UPS Control Command DescriptionUPS Control UPS Control UPS Characteristics Call-UPS II will not allow changes to UPS characteristics Sensitivity of the UPS to power line fluctuation. Set this With Symmetra Power Array UPS Characteristics Symmetra Power Array Setting Description Menu Data/Event LoggingDATA/EVENT Logging Default DescriptionCALL-UPS Call-UPS SettingsCALL-UPS II Settings CALL-UPS II Settings Default Description Site IDspace charactertrouble code Paging SetupPaging Setup Paging Setup Setting Default Description Event Description Paging Setup EventsProbe Measure-UPS InfoMEASURE-UPS Info Problem Possible Cause Solution Problem ResolutionTroubleshooting Chart TroubleshootingIf Problems Persist Pin Function SpecificationsManagement Port Pinout Environmental Product SpecificationsElectrical PhysicalTriple Chassis Appendix Multiple SmartSlot InstallationDevice Priority Position Smart-UPS and Matrix-UPS Symmetra Power ArrayDaisy Chains Page Page Page Limited Warranty Toll free technical support