UPS CONTROL (Continued)

 

 

Command

Description

 

 

 

Causes the UPS to shut down. Call-UPS II immediately

Graceful Turn

signals that the UPS is on battery and that the battery is

nearly exhausted. Graceful Turn OFF uses the value set for

OFF

Low Battery Duration. See UPS Characteristics table in

 

 

Sec. 4.4.

 

 

 

Starts and stops runtime calibration on the UPS.

 

Calibration starts only if the UPS has a 100% battery

 

charge. If the UPS accepts the command to start runtime

Start(Stop)

calibration, Call-UPS II reports “Runtime Calib: OK.” If

Runtime

the UPS does not accept the command, Call-UPS II

Calibration

reports “Runtime Calib: NO.” Runtime is displayed on the

 

UPS Status [and Diagnostics] Screen. Note: Smart-UPS

 

products with serial numbers that begin with the letter W

 

do not support runtime calibration.

 

 

Put UPS in

For Matrix-UPS and Symmetra Power Array only. Puts the

(Return from)

UPS in Bypass mode and returns the UPS from Bypass

Bypass

mode.

 

 

If the UPS is powered off when UPS Control is selected from the Main menu, Call-UPSII responds with an abbreviated control menu:

--------------------- CONTROL MENU ----------------------

1- Turn UPS ON

2- Turn UPS OFF ?- Help

<ENTER> Display menu

<ESC> Return to Previous menu

>

Type 1 to turn the UPS on, then press ESC to return to the Main menu or press ENTER to re-display the full UPS Control menu.

21

Image 25
Contents Call-UPSII Thank You Contents Problem Resolution Overview IntroductionHardware Requirements Call-UPS II Panel Product DescriptionManagement Port UPS Monitoring Port External VersionUPS Cable External Version Power Port External VersionWith Smart-UPS With Matrix-UPS Status LED Indication Status IndicatorInstallation Installation and SetupHandling Receiving InspectionExternal Version Confirm OperationInitial Logging On Configure Call-UPSPress any key to bring up the Main menu Customize SettingsConnect to Modem SmartSlot Configuration External Configuration Operation UPS Status and DiagnosticsLogging On to Call-UPS With Smart-UPS and Matrix-UPS UPS Status Smart-UPS and Matrix-UPS Description Sleeping Inverter Shutdown UPS Status and Diagnostics Symmetra Power Array Description With Symmetra Power ArrayUPS Status and Diagnostics Page RIM Page UPS Control Command DescriptionUPS Control UPS Control UPS Characteristics Call-UPS II will not allow changes to UPS characteristics Sensitivity of the UPS to power line fluctuation. Set this With Symmetra Power Array UPS Characteristics Symmetra Power Array Setting Description Menu Data/Event LoggingDATA/EVENT Logging Default DescriptionCALL-UPS Call-UPS SettingsCALL-UPS II Settings CALL-UPS II Settings Default Description Site IDspace charactertrouble code Paging SetupPaging Setup Paging Setup Setting Default Description Event Description Paging Setup EventsProbe Measure-UPS InfoMEASURE-UPS Info Troubleshooting Chart Problem ResolutionTroubleshooting Problem Possible Cause SolutionIf Problems Persist Management Port Pinout SpecificationsPin Function Electrical Product SpecificationsPhysical EnvironmentalDevice Priority Position Appendix Multiple SmartSlot InstallationTriple Chassis Daisy Chains Symmetra Power ArraySmart-UPS and Matrix-UPS Page Page Page Limited Warranty Toll free technical support