UPS STATUS (Smart-UPS and Matrix-UPS)
Item | Description | |
|
| |
Utility Line | Utility line input, in volts AC RMS. | |
|
| |
UPS Output | UPS output to the load, in volts AC RMS. | |
|
| |
UPS Load | Connected load as a percentage of the rated capacity of the UPS. | |
|
| |
Run Time | Estimate of the total run time currently available from the | |
UPS, based on present load and battery, in minutes. | ||
| ||
|
| |
Load Power | Amount of power being drawn by the load, in | |
supported by the UPS). | ||
| ||
|
| |
Load Current | Amount of current being drawn by the load, in amps (if | |
supported by the UPS). | ||
|
| |
UPS Temp | Current temperature inside the UPS, in degrees Celsius. | |
|
| |
Freq | Output frequency of the UPS, in hertz. | |
|
| |
| Reason for the last UPS transfer to battery. Possible results | |
Last Xfer | are: Test, Low Voltage, Hi Voltage, Rate of Change, and | |
| Notch/Spike. | |
|
| |
Voltage | Total voltage of the UPS batteries, in volts DC. | |
|
| |
Capacity | Battery charge as a percentage of capacity. | |
|
| |
Smart Cells | Number o f Smart Cell battery packs connected to the UPS | |
(only with | ||
| ||
|
| |
Bad Cells | Number of Smart Cells connected to the UPS that have gone | |
bad (only with | ||
| ||
|
| |
Batt Date | Date of the last battery change. | |
|
| |
| Results o f the last UPS | |
Self Test | None (not available), Unable to Test (invalid results due to | |
| overload), and Battery Failed (due to insufficient capacity). | |
|
|
13