APC AP9208 With Symmetra Power Array, UPS Status and Diagnostics Symmetra Power Array Description

Page 19

With Symmetra Power Array

Type 1, then ENTER at the Main menu to display the Status and Diagnos- tics screen of the connected Symmetra Power Array.

-----------------------------

SYMMETRA STATUS

-------------------------------

IM Status: On & Ok

 

 

 

Last Xfer: None

 

RIM Status: Off & Failed

 

Last Self test: OK

 

------------------------------

INPUT/OUTPUT ---------------------------------

 

Input:

246.0 V at 60.04 Hz

Load Assuming No Redundancy: 000 %

Output:

000.0 V at 60.04 Hz

Allowing for n+1 Redundancy: 000 %

Load Current:

00.0 A

 

 

 

Capacity:

16.0 kVA

 

 

 

 

 

Alarm if Over: 06.0 kVA

-----------------------------

POWER MODULES ---------------------------------

 

Installed:

05

 

 

 

Fault Tolerance:

n+0

Bad:

00

 

 

 

Alarm if Under:

n+2

-------------------------------

BATTERIES -----------------------------------

 

Installed:

004

Voltage:

137.1 VDC

Runtime: 0244 min.

Bad:

000

Capacity:

98.0 %

Alarm if Under: 015 min.

System Status:On-Line

1- Main Frame Information

2- External Battery Frame Information for frame(s): 1, 2, 3, 6, 7 <ENTER>=Refresh, <ESC>=Main menu>, ?=Help>

The following table describes the items on the UPS Status and Diagnos- tics screen when Call-UPSII is used with a Symmetra Power Array. The table continues on the next page.

UPS STATUS AND DIAGNOSTICS (Symmetra Power Array)

Item

Description

 

 

IM Status

Status of the Intelligence Module.

 

 

RIM Status

Status of the Redundant Intelligence Module.

 

 

 

Reason for the last UPS transfer to battery. Possible

Last Xfer

results are: Test, Low Voltage, HiVoltage, Rate of

 

Change, and Notch/Spike.

 

 

Last Self Test

Results of the last Self Test. Possible results are listed

in earlier Self Test Table in this section.

 

 

 

Input

Utility line input, in volts AC RMS and in hertz.

 

 

Output

UPS output to the load, in volts AC RMS and in hertz.

 

 

Load Current

Amount of current being drawn by the load, in amps.

 

 

15

Image 19
Contents Call-UPSII Thank You Contents Problem Resolution Overview IntroductionHardware Requirements UPS Monitoring Port External Version Product DescriptionCall-UPS II Panel Management PortUPS Cable External Version Power Port External VersionWith Smart-UPS With Matrix-UPS Status LED Indication Status IndicatorReceiving Inspection Installation and SetupInstallation HandlingExternal Version Confirm OperationInitial Logging On Configure Call-UPSPress any key to bring up the Main menu Customize SettingsConnect to Modem SmartSlot Configuration External Configuration Operation UPS Status and DiagnosticsLogging On to Call-UPS With Smart-UPS and Matrix-UPS UPS Status Smart-UPS and Matrix-UPS Description Sleeping Inverter Shutdown UPS Status and Diagnostics Symmetra Power Array Description With Symmetra Power ArrayUPS Status and Diagnostics Page RIM Page UPS Control Command DescriptionUPS Control UPS Control UPS Characteristics Call-UPS II will not allow changes to UPS characteristics Sensitivity of the UPS to power line fluctuation. Set this With Symmetra Power Array UPS Characteristics Symmetra Power Array Setting Description Menu Data/Event LoggingDATA/EVENT Logging Default DescriptionCALL-UPS Call-UPS SettingsCALL-UPS II Settings CALL-UPS II Settings Default Description Site IDspace charactertrouble code Paging SetupPaging Setup Paging Setup Setting Default Description Event Description Paging Setup EventsProbe Measure-UPS InfoMEASURE-UPS Info Problem Possible Cause Solution Problem ResolutionTroubleshooting Chart TroubleshootingIf Problems Persist Management Port Pinout SpecificationsPin Function Environmental Product SpecificationsElectrical PhysicalDevice Priority Position Appendix Multiple SmartSlot InstallationTriple Chassis Daisy Chains Symmetra Power ArraySmart-UPS and Matrix-UPS Page Page Page Limited Warranty Toll free technical support