APC AP9608, AP9208 manual Paging Setup, Site IDspace charactertrouble code

Page 36

4.7 Paging Setup

When used in conjunction with a modem that understands industry stan- dard AT commands, Call-UPSII can be set up to page an operator in case of trouble, such as on-battery operation or problems with the UPS. To use paging, choose item 6 on the Main menu menu to bring up the Paging Setup menu. Select items from the Paging Setup menu, referring to the screen listing and table later in this section.

Call-UPSII reports the condition by showing a code on the pager’s dis- play. Call-UPSII reports information in this format:

[Site ID][space character][trouble code]

Site ID, Space Character, and Trouble Code are among the settings pro- grammed by the user (see below). When a reportable condition occurs, Call-UPSII uses the modem to page an operator. Call-UPSII issues a mo- dem command string like this:

The initial AT comes from Call-UPS II. Do not include it in the Dial String. In this example, the Dial String is DT9,5551212@. DT instructs the modem to dial in tone mode. The 9 and comma are only needed when Call-UPSII is used with a phone system that requires dialing 9 for an out- side line. The comma adds a pause. The @ symbol at the end of the pager phone number sets the modem to “wait for quiet answer” (five seconds

of silence) before entering the number to send to the pager. The 12345678 in the example comes from item number 8, Site ID, on the Call-UPSII Paging Setup menu. Call-UPSII then issues the Space Character and Trouble Code shown near the end of the example. For this example, the pager would show:

12345678 1

Call-UPSII also issues the semicolon at the end of the modem command. This sends the modem back into command state.

32

Image 36
Contents Call-UPSII Thank You Contents Problem Resolution Introduction OverviewHardware Requirements Product Description Call-UPS II PanelManagement Port UPS Monitoring Port External VersionPower Port External Version UPS Cable External VersionWith Smart-UPS With Matrix-UPS Status Indicator Status LED IndicationInstallation and Setup InstallationHandling Receiving InspectionConfirm Operation External VersionConfigure Call-UPS Initial Logging OnCustomize Settings Press any key to bring up the Main menuConnect to Modem SmartSlot Configuration External Configuration UPS Status and Diagnostics OperationLogging On to Call-UPS With Smart-UPS and Matrix-UPS UPS Status Smart-UPS and Matrix-UPS Description Sleeping Inverter Shutdown With Symmetra Power Array UPS Status and Diagnostics Symmetra Power Array DescriptionUPS Status and Diagnostics Page RIM Page Command Description UPS ControlUPS Control UPS Control UPS Characteristics Call-UPS II will not allow changes to UPS characteristics Sensitivity of the UPS to power line fluctuation. Set this With Symmetra Power Array UPS Characteristics Symmetra Power Array Setting Description Data/Event Logging MenuDefault Description DATA/EVENT LoggingCall-UPS Settings CALL-UPSCALL-UPS II Settings CALL-UPS II Settings Default Description Paging Setup Site IDspace charactertrouble codePaging Setup Paging Setup Setting Default Description Paging Setup Events Event DescriptionMeasure-UPS Info ProbeMEASURE-UPS Info Problem Resolution Troubleshooting ChartTroubleshooting Problem Possible Cause SolutionIf Problems Persist Specifications Management Port PinoutPin Function Product Specifications ElectricalPhysical EnvironmentalAppendix Multiple SmartSlot Installation Device Priority PositionTriple Chassis Symmetra Power Array Daisy ChainsSmart-UPS and Matrix-UPS Page Page Page Limited Warranty Toll free technical support