Digital Energy™ LP Series
4.5.2 Available input voltages: hardware modifications
The following input voltages are possible: 208, 240 Vac (see 4.5.2.1) and 120 Vac (see 4.5.2.2)
4.5.2.1Input voltage 208 or 240Vac.
1.Input voltage is 208 Vac. This is the factory setting. Proceed with step 3.
2.Input voltage is 240Vac. In this case the bypass tap on the output transformer must be changed. Please refer to fig. 8 and 8a. Proceed as follows:
2.1Remove the yellow wire B from faston 74 (connect) and place this wire on faston 72 (park).
2.2Remove the blue wire A from faston 61 (park) and place this wire on faston 74 (connect).
Bypass tap factory setting: 208 Volt
(park)
(park)
(connect)
Bypass tap changed to 240 Volt
(park)
(park)
(connect)
Figure 8. LP | Figure 8a. LP |
Bypass tap change | Rear view |
3.Connect the utility supply wires to terminals 6 (L1), 7 (L2) and 8 (equipment grounding conductor). See figure 9. Ground connection is essential!
If a neutral wire is part of the site wiring provided, we suggest to isolate this wire for future use or other applications.
Figure 9. LP 5/6/8/10-11U:
Output (grey) / input terminals
4.For the output voltage proceed with 4.5.3.
LX: OPM_LPU_11U_5K0_10K_1US_V030 | 13 | GE DE LP 11U UPS: Installation / User Manual 3.0 (US) |