GE LP11U user manual Input voltage 120Vac optional, 5/6kVA only, Output voltage 208Vac

Page 16

g

Digital EnergyLP Series

4.5.2.2Input voltage 120Vac (optional, 5/6kVA only).

LP-UUPS equipped with an (optional) step-up transformer (5/6kVA models only) can be connected to an input voltage of 120Vac.

1.Connect the utility supply wires to terminals L, N and GND (equipment grounding conductor). See figure 10. Ground connection is essential!

Figure 10. LP 5/6-11U: 120Vac Input terminals

2.For the output voltage proceed with 4.5.3.

4.5.3 Available output voltages: hardware modifications

The off-factory setting is 208 Vac: a link is placed between terminals 2 and 3. An extra link was delivered with the unit (in a plastic bag) to enable other output voltages (5/6kVA models only).

The following voltages are available: 120, 208, 220, 230, 240 Vac.

4.5.3.1Output voltage 208Vac

This is the off-factory setting. There is a link between terminal 2 and 3.

1.Connect the output wires to the terminals 1 (L1) and 4 (L2).

2.Connect the ground wire to terminal 5. Ground connection is essential! See figure 11.

Figure 11. LP 5/6/8/10-11U: 208 Vac output connection

3.Return to either 4.5.1.1 step 5 or 4.5.1.2 step 5

LX: OPM_LPU_11U_5K0_10K_1US_V030

14

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 16
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Installation Important Safety InstructionsGeneral Storage BatteriesIntroduction WarrantyDescription Functional Explanation Principles of OperationAutomatic Bypass Switch Installation Package ContentsTransport Unpacking LocationOutput voltage UPS model 120V 208V 240V Utility voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap factory setting 208 Volt Available input voltages hardware modificationsInput voltage 208 or 240Vac Bypass tap changed to 240 VoltAvailable output voltages hardware modifications Input voltage 120Vac optional, 5/6kVA onlyOutput voltage 208Vac Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacSetup Screens Input VoltageInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterMaintenance ECO-modeNo-load shutdown Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressBattery 23C UseInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSStatus and Alarm Menu On Line Alarm Press UPTemp TOO High Battery Depleted Battery Charger no Float Capacitor C1 Capacity LOWInverter OFF Service Screens Service MenuInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Language English Input Voltage Output Voltage Output FrequencyFrequency Range 2% PLL Lock Speed Normal FAN CurveQuick Battery Test Start Automatic Bypass Enabled Service Warning DisabledTest Screens Procedure Deep Battery TestCalibrate BAT Test Activated Other Features Overload protection in bypass modeShutdown Utility startSuperior Battery Management ECOAuto Restart OFF Press Enter Auto restartInterfacing Features RS232 / contact interfaceEmergency shutdown Relay Card optional Snmp Interface optionalOptional Features Extended RuntimePlug-in Cards RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsMaintenance SafetyRecycling the UPS at the end of service life Cooling fanSelftest Failure Temp TOO High TroubleshootingSelftest Failure Q4 not OK Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input