GE LP11U user manual Setup Screens, Input Voltage Change to, Output Voltage

Page 19

g

Digital EnergyLP Series

For LP 8/10kVA:

8.Remove all links between the terminals.

9.Split both the load wires and spread one wire over terminal 1-2 and the other over 3-4 respectively.

10.Connect the ground wire to terminal 5. Ground connection is essential! See figure 15a.

11.Return to either 4.5.1.1 step 5 or 4.5.1.2 step 5

Figure 15a. Output cable splitting for

8/10kVA 120V 2-wire

4.5.4 Input/output voltages: Software modification.

NOTE: following this procedure you realize that the values shown in the LCD match the actual input/output voltages.

1.Switch on the circuit breakers 'utility' (8) and 'bypass' (9) (see also section 5.2, step 1-2)

2.Go to the set-up menu. See 5.3.4 ‘Set-up Menu’

SETUP SCREENS

ENTER/RESET exit

3.Using the push-buttons 'up' and 'down' you can scroll through the several set-up screens. 'Enter/Reset' confirms the screen choice. Go to the set-up screen 'INPUT VOLTAGE'.

INPUT VOLTAGE 208V

4.Here you can change the input voltage to 240 Volt. The value of the input voltage blinks. Scroll through its settings by using the push-buttons 'up' and 'down', the new setting is confirmed by pressing 'Enter/Reset'.

INPUT VOLTAGE

CHANGE TO 240V

5.Go to the set-up screen 'OUTPUT VOLTAGE'.

OUTPUT VOLTAGE

208V

6.Here you can change the output voltage to 240 Volt. The value of the input voltage blinks. Scroll through its settings by using the push-buttons 'up' and 'down', the new setting is confirmed by pressing 'Enter/Reset'.

INPUT VOLTAGE

CHANGE TO 240V

7.To return to the default screen scroll to the set-up screens first and press 'Enter/Reset'. You can also wait 20 seconds: the time-out period of no key activity.

8.You can now proceed with 5.1 or 5.2.

LX: OPM_LPU_11U_5K0_10K_1US_V030

17

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 19
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Installation Important Safety InstructionsGeneral Batteries StorageIntroduction WarrantyDescription Principles of Operation Functional ExplanationAutomatic Bypass Switch Location InstallationPackage Contents Transport UnpackingOutput voltage UPS model 120V 208V 240V Utility voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap changed to 240 Volt Bypass tap factory setting 208 VoltAvailable input voltages hardware modifications Input voltage 208 or 240VacAvailable output voltages hardware modifications Input voltage 120Vac optional, 5/6kVA onlyOutput voltage 208Vac LP 5/6/8/10-11U Output tap change Output voltage 120Vac split-phaseOutput voltage 220/230/240Vac Output voltage 120Vac single phaseOutput Voltage Setup ScreensInput Voltage Input Voltage Change toLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Press Enter Autorestart OFF Setting MismatchManual bypass MaintenanceECO-mode No-load shutdownDescription of Front and Rear Panel OperationRear panel Step-up transformer Rear panel of the step-up transformerSelftest Progress Start-upAutonomy Time Left Operating Time 0YEAR 29DAYS Battery 23CUse Input LineStatus and Alarm Menu On Line Alarm Press UPTemp TOO High Battery Depleted Battery Charger no Float Capacitor C1 Capacity LOWInverter OFF Software Version R2.9 FAN Speed INV.DC + Service ScreensService Menu Input and Output not SynchronizedTstamp Q4 Automatic Bypass EnabledFAN Curve Language English Input Voltage Output VoltageOutput Frequency Frequency Range 2% PLL Lock Speed NormalQuick Battery Test Start Automatic Bypass Enabled Service Warning DisabledTest Screens Procedure Deep Battery TestCalibrate BAT Test Activated Utility start Other FeaturesOverload protection in bypass mode ShutdownAuto restart Superior Battery ManagementECO Auto Restart OFF Press EnterRelay Card optional Snmp Interface optional Interfacing FeaturesRS232 / contact interface Emergency shutdownRPA-Facility Redundant Parallel Architecture Optional FeaturesExtended Runtime Plug-in CardsSeismic anchors PDM Power Distribution ModuleCooling fan MaintenanceSafety Recycling the UPS at the end of service lifeSelftest Failure Temp TOO High TroubleshootingSelftest Failure Q4 not OK UPS Type 11U 10-11U SpecificationsAutomatic Bypass Switch Enclosure Center of Gravity Dimensions Conduit BoxLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input