GE LP11U user manual Test Screens, Automatic Bypass Enabled Service Warning Disabled

Page 33
TEST ACTIVATED
TEST SUCCESSFUL TEST FAILED NOT AVAILABLE

g

AUTOMATIC BYPASS

ENABLED

SERVICE WARNING

DISABLED

Digital EnergyLP Series

Controls functioning of the automatic bypass switch. Range: ENABLED/DISABLED. If the UPS is used as a frequency converter you may change the setting to ‘DISABLED’. Bypass operation will then be inhibited and all alarms related to ‘bypass out of limits’ are suppressed.

The system can prompt for service to a user defined schedule.

Range: 8/12/16/20/24/28 months or DISABLED. To reset the timer: first select “DISABLED” and subsequently set a new alarm interval.

5.4Test Screens

These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS monitoring software (RS232/SNMP). The upper line indicates the kind of test, the second line its status.

Upper lines:

second line:

 

GENERAL SYSTEM

TEST START

the test will start soon

QUICK BATTERY

TEST ACTIVATED

the test is running

CALIBRATE BAT

TEST SUCCESFUL

the test has been completed succesfully

BYPASS

TEST FAILED

the test has not been completed succesfully

5.4.1 Battery Test, general

Automatic test: Every 500 operating hours the UPS conducts automatic battery tests to ensure that the batteries and the wiring are able to support power failures. The tests do not cause any interruption in the functioning of the unit.

Manual test: A manual battery test can be activated

-either through an interface kit, via the RS232 or SNMP Interface Port (please refer to the manual of your interface package), or

-via the front panel: see below

5.4.2Quick Battery Test

From the standard menu first enter the service menu (press the 'down' and 'Enter/Reset' keys simultaneously, then press the 'down' key until the following screen appears:

QUICK BATTERY

TEST PRESS ENTER

The ‘Enter/Reset’ key confirms the selection, and the screen shows:

QUICK BATTERY

TEST START

The test status (indicated by the second line) can be:

= testing

= battery has been tested with positive result

= the batteries should be replaced

= battery capacity too low to start the test

If the batteries are dangerously close to being worn out, a low priority alarm 'replace battery' will be generated. The batteries must be replaced as soon as possible (see section 8.3).

NOTE: If the manual test is started immediately after installation or after a power failure, the UPS may generate a false 'replace battery' alarm as the batteries have been (partly) discharged during transport/storage or during the power failure.

LX: OPM_LPU_11U_5K0_10K_1US_V030

31

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 33
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Important Safety Instructions InstallationGeneral Batteries StorageWarranty IntroductionDescription Principles of Operation Functional ExplanationAutomatic Bypass Switch Package Contents InstallationTransport Unpacking LocationUtility voltage UPS model 120V 208V 240V Output voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Available input voltages hardware modifications Bypass tap factory setting 208 VoltInput voltage 208 or 240Vac Bypass tap changed to 240 VoltInput voltage 120Vac optional, 5/6kVA only Available output voltages hardware modificationsOutput voltage 208Vac LP 5/6/8/10-11U Output tap change Output voltage 120Vac split-phaseOutput voltage 220/230/240Vac Output voltage 120Vac single phaseInput Voltage Setup ScreensInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Press Enter Autorestart OFF Setting MismatchECO-mode MaintenanceNo-load shutdown Manual bypassDescription of Front and Rear Panel OperationRear panel Step-up transformer Rear panel of the step-up transformerSelftest Progress Start-upUse Battery 23CInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSOn Line Alarm Press UP Status and Alarm MenuTemp TOO High Battery Charger no Float Capacitor C1 Capacity LOW Battery DepletedInverter OFF Service Menu Service ScreensInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Tstamp Q4 Automatic Bypass EnabledOutput Frequency Language English Input Voltage Output VoltageFrequency Range 2% PLL Lock Speed Normal FAN CurveAutomatic Bypass Enabled Service Warning Disabled Quick Battery Test StartTest Screens Deep Battery Test ProcedureCalibrate BAT Test Activated Overload protection in bypass mode Other FeaturesShutdown Utility startECO Superior Battery ManagementAuto Restart OFF Press Enter Auto restartRS232 / contact interface Interfacing FeaturesEmergency shutdown Relay Card optional Snmp Interface optionalExtended Runtime Optional FeaturesPlug-in Cards RPA-Facility Redundant Parallel ArchitectureSeismic anchors PDM Power Distribution ModuleSafety MaintenanceRecycling the UPS at the end of service life Cooling fanTroubleshooting Selftest Failure Temp TOO HighSelftest Failure Q4 not OK UPS Type 11U 10-11U SpecificationsAutomatic Bypass Switch Enclosure Center of Gravity Dimensions Conduit BoxLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input