5.The right option slot (14) at the rear of the unit contains the the RPA-card. Before the parallel system can be put into operation a unique number has to be appointed to each UPS in the system. This can be 0, 1,

2 or 3. Start with 0 for the first unit, 1 for the second, 2 for the third and 3 for the last unit:

-loosen the screws, remove the RPA-card

-set the dipswitch to the appointed number (fig. 18)

-re-install the RPA-card, fasten the screws.

Do NOT install the network cables between the RPA-cards of the units yet!

Figure 18. Appointing a unique number to each UPS in the system

6.In the UPS many parameters can be set. It is advised to keep the same setting for each parameter in each UPS in the parallel system. In any case the following parameters are critical and should have equal settings:

-autorestart (on/off, see 5.3.3)

-output voltage (120/208/220/230/240 Vac, see 5.3.4)

-output frequency (50/60 Hz, see 5.3.4)

It is absolutely required that these parameters are set to the same value. Off factory this is the case. If you’re not sure that the units have equal settings:

-be sure that the RPA-cards of the units have not been interconnected yet

-be sure that utility power is connected to the UPS

-start each unit individually (see 5.2), check / change the parameters, and switch the unit off again.

7.Interconnect the RPA-cards of the units, using the network cable that came with the UPS. See figure 17 (dotted line). Only install the cables that were delivered with the UPSs! Of the first and the last UPS in the system only one RPA-socket is used to interconnect the UPSs. A bus terminator must be placed in the other (free) RPA-socket. The required bus terminators have been delivered with the unit.

4.5.6.2 Notes concerning starting up the parallel system

For starting up the system please refer to section 5.2.

After switching on all units the LP UPSs will show the following display:

AUTORESTART OFF

PRESS ENTER

After pressing the ‘Enter/Reset’ button on one of the units the system will start up. All units will display the standard screen. The number in the lower right corner indicates the number of the UPS in the system.

LP 5-11U

 

LOAD 40%

2

If the parameters mentioned in 4.5.6.1 step 6 are not set to the same value the UPS will display the following screen after start-up:

AUTORESTART OFF

SETTING MISMATCH

In this case check and correct the setting of the parameters as mentioned in 4.5.6.1, step 6.

LX: OPM_LPU_11U_5K0_10K_1US_V030

20

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 22
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Installation Important Safety InstructionsGeneral Storage BatteriesIntroduction WarrantyDescription Functional Explanation Principles of OperationAutomatic Bypass Switch Transport Unpacking InstallationPackage Contents LocationOutput voltage UPS model 120V 208V 240V Utility voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Input voltage 208 or 240Vac Bypass tap factory setting 208 VoltAvailable input voltages hardware modifications Bypass tap changed to 240 VoltAvailable output voltages hardware modifications Input voltage 120Vac optional, 5/6kVA onlyOutput voltage 208Vac Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacInput Voltage Change to Setup ScreensInput Voltage Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterNo-load shutdown MaintenanceECO-mode Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressInput Line Battery 23CUse Autonomy Time Left Operating Time 0YEAR 29DAYSStatus and Alarm Menu On Line Alarm Press UPTemp TOO High Battery Depleted Battery Charger no Float Capacitor C1 Capacity LOWInverter OFF Input and Output not Synchronized Service ScreensService Menu Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Frequency Range 2% PLL Lock Speed Normal Language English Input Voltage Output VoltageOutput Frequency FAN CurveQuick Battery Test Start Automatic Bypass Enabled Service Warning DisabledTest Screens Procedure Deep Battery TestCalibrate BAT Test Activated Shutdown Other FeaturesOverload protection in bypass mode Utility startAuto Restart OFF Press Enter Superior Battery ManagementECO Auto restartEmergency shutdown Interfacing FeaturesRS232 / contact interface Relay Card optional Snmp Interface optionalPlug-in Cards Optional FeaturesExtended Runtime RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsRecycling the UPS at the end of service life MaintenanceSafety Cooling fanSelftest Failure Temp TOO High TroubleshootingSelftest Failure Q4 not OK Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input