5.2Start-up

The numbers between (brackets) refer to figure 19 in section 5.1.

Note: the UPS can be started on battery power if the utility input voltage is not available or if circuit

breaker ‘utility’ is in off-position: simply skip step 1. To prevent accidental discharging of the batteries, it is however recommended to proceed with step 1 and start the unit only when the utility input voltage is available.

1.Turn breaker 'utility' (8) and breaker 'bypass' (9), both on the rear panel, into position ‘on’ (up).

2.Some UPS parameters (e.g. voltage, frequency, LCD language) are user selectable. If you want to change one or more settings, please refer to section 5.3.4 ‘Set-up Menu’ now. Changing the settings later is possible, however only after switching off the unit.

3.Turn switch 'UPS on/off' (rear panel, 7) into position ‘on’ (up). The green LED 'operation' (front panel, 5) will illuminate.

After switching on the UPS performs a self-test and the display (front panel, 1) will show:

SELFTEST

IN PROGRESS

After completion of the self-test the output voltage of the UPS is available and the unit is ready for use. The display will show the default screen: model and actual load (values are examples)

LP 5-11U

LOAD 37%

In case of a system failure the self-test results in a failure message; this message is displayed for 30 seconds before the self-test is repeated automatically. If the faulty situation persists, switch off the UPS and contact your dealer. See chapter 9 for more information.

4.Though the batteries (the internal energy reserve) were fully charged when the UPS left the factory, they might have lost some energy during transport and/or storage. It is recommended to allow the UPS to recharge the batteries for a few hours. This way you ensure that the UPS can provide sufficient runtime in case of a utility power failure.

5.If not yet switched on, the equipment connected to the UPS can be switched on now; operate as usual.

LX: OPM_LPU_11U_5K0_10K_1US_V030

24

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 26
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features General Important Safety InstructionsInstallation Storage BatteriesDescription WarrantyIntroduction Functional Explanation Principles of OperationAutomatic Bypass Switch Transport Unpacking InstallationPackage Contents LocationUPS model Tightening torque force Utility voltage UPS model 120V 208V 240VOutput voltage UPS model 120V 208V 240V LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Input voltage 208 or 240Vac Bypass tap factory setting 208 VoltAvailable input voltages hardware modifications Bypass tap changed to 240 VoltOutput voltage 208Vac Input voltage 120Vac optional, 5/6kVA onlyAvailable output voltages hardware modifications Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacInput Voltage Change to Setup ScreensInput Voltage Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterNo-load shutdown MaintenanceECO-mode Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressInput Line Battery 23CUse Autonomy Time Left Operating Time 0YEAR 29DAYSTemp TOO High On Line Alarm Press UPStatus and Alarm Menu Inverter OFF Battery Charger no Float Capacitor C1 Capacity LOWBattery Depleted Input and Output not Synchronized Service ScreensService Menu Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Frequency Range 2% PLL Lock Speed Normal Language English Input Voltage Output VoltageOutput Frequency FAN CurveTest Screens Automatic Bypass Enabled Service Warning DisabledQuick Battery Test Start Calibrate BAT Test Activated Deep Battery TestProcedure Shutdown Other FeaturesOverload protection in bypass mode Utility startAuto Restart OFF Press Enter Superior Battery ManagementECO Auto restartEmergency shutdown Interfacing FeaturesRS232 / contact interface Relay Card optional Snmp Interface optionalPlug-in Cards Optional FeaturesExtended Runtime RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsRecycling the UPS at the end of service life MaintenanceSafety Cooling fanSelftest Failure Q4 not OK TroubleshootingSelftest Failure Temp TOO High Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input