GE LP11U Language English Input Voltage Output Voltage, Output Frequency, FAN Curve, Set-up Menu

Page 32

g

Digital EnergyLP Series

5.3.4 Set-up Menu

To enter the set-up menu:

1.Be sure the UPS is switched off.

2.Press push-button 'Enter/Reset' (front panel) and then turn switch ‘UPS on/off’ (rear panel) into position ‘on’ (up). Keep Enter/Reset pressed until set-up menu appears.

Using push-buttons 'up' and 'down' you can scroll through the several set-up screens, 'Enter/Reset' confirms a screen choice. After selecting a set-up screen you can scroll through its settings using the push-buttons 'up' and 'down', a setting is confirmed by pressing 'Enter/Reset'. To abort the set-up procedure (i.e. without changing the setting) just wait the 20 seconds time-out period after which the default screen will return.

SETUP SCREENS ENTER/RESET exit

WARNING: OUTPUT CHANGES ON LINE

LANGUAGE

ENGLISH

INPUT VOLTAGE 208V

OUTPUT VOLTAGE

208V

OUTPUT FREQUENCY

60.0Hz

FREQUENCY RANGE 2%

PLL LOCK SPEED

NORMAL

BATTERY CAPACITY 7Ah

FAN CURVE 0

NO-LOAD SHUTDOWN YES

The intro set-up screen. 'Enter/Reset' returns to the default screen. You can also wait 20 seconds: the time-out period of no key activity.

Pressing ‘up’ displays the screens in the following order:

A short reminder that the new settings will be valid immediately after depressing the ‘Enter/Reset’ key.

Changes the language of the screen messages: you can select English, German, French, Italian, Spanish.

The system input voltage: Range 120/208/240 Vac.

The system output voltage. Range: 120/208/220/230/240 Vac.

The system output frequency. Range: 50/60 Hz.

WARNING! Changing of the output frequency can cause severe damage of equipment connected to the UPS: Be sure that the new frequency is suitable for the connected equipment.

The frequency tracking range (in which the output converter frequency will follow the bypass frequency). Range: 2/4/6 %.

If the bypass frequency is beyond the setting, the output converter will return to the fixed crystal controlled frequency.

The frequency tracking speed range (in which the output converter frequency will follow the bypass frequency).

Range: NORMAL (1Hz/sec), HIGH (5Hz/sec).

Battery capacity. Range: 7 through 590 Ah, in 1 Ah steps.

WARNING! If you proceed, the information about the actual battery condition (as a result of a deep battery test) is lost. For more info see section 5.4.3 'Deep Battery Test'.

The fan speed. Range: 0 / 1. Proper setting optimizes the cooling capacity of the fans installed. DO NOT READJUST! Incorrect setting may lead to reduced lifetime of the power semiconductors.

Setting ‘YES’ means that the function is activated: the UPS will switch off during a utility failure when the load is less than 2% of the maximum load. Range: YES/NO.

NOTE: if the UPS operates in parallel the no-load shutdown function is not

available. In this case do not activate this function: its setting should read "NO".

LX: OPM_LPU_11U_5K0_10K_1US_V030

30

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 32
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features General Important Safety InstructionsInstallation Storage BatteriesDescription WarrantyIntroduction Functional Explanation Principles of OperationAutomatic Bypass Switch Installation Package ContentsTransport Unpacking LocationUPS model Tightening torque force Utility voltage UPS model 120V 208V 240VOutput voltage UPS model 120V 208V 240V LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap factory setting 208 Volt Available input voltages hardware modificationsInput voltage 208 or 240Vac Bypass tap changed to 240 VoltOutput voltage 208Vac Input voltage 120Vac optional, 5/6kVA onlyAvailable output voltages hardware modifications Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacSetup Screens Input VoltageInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterMaintenance ECO-modeNo-load shutdown Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressBattery 23C UseInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSTemp TOO High On Line Alarm Press UPStatus and Alarm Menu Inverter OFF Battery Charger no Float Capacitor C1 Capacity LOWBattery Depleted Service Screens Service MenuInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Language English Input Voltage Output Voltage Output FrequencyFrequency Range 2% PLL Lock Speed Normal FAN CurveTest Screens Automatic Bypass Enabled Service Warning DisabledQuick Battery Test Start Calibrate BAT Test Activated Deep Battery TestProcedure Other Features Overload protection in bypass modeShutdown Utility startSuperior Battery Management ECOAuto Restart OFF Press Enter Auto restartInterfacing Features RS232 / contact interfaceEmergency shutdown Relay Card optional Snmp Interface optionalOptional Features Extended RuntimePlug-in Cards RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsMaintenance SafetyRecycling the UPS at the end of service life Cooling fanSelftest Failure Q4 not OK TroubleshootingSelftest Failure Temp TOO High Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input