Digital EnergyLP Series

8 - Maintenance

8.1General

When used properly, the UPS is virtually maintenance free other than keeping the air inlets/outlets free from dust.

8.2Cooling fan

The expected operational life of the cooling fans is approximately 20,000 to 40,000 hours of continuous operation. A high ambient temperature will shorten this operational life.

8.3Batteries

The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the number of discharge cycles.

As a healthy battery is essential to the performance of the UPS, an automatic battery test is performed regularly to ensure failsafe operation (see section 5.4.1). When the condition of the battery is critical, the warning signal will be activated (buzzer 1x per 8 secs, and alarm message 'Replace battery', see 5.3.2). The batteries must be replaced as soon as possible. Please contact your dealer. Use only UL recognised batteries (BAZR2), valve

regulated types.

NOTE: under certain circumstances a manual battery test can result in a false alarm: please see section 5.4.2

'QUICK BATTERY TEST'.

Regular deep battery tests are advised in order to re-calibrate the capacity of aging batteries. See section 5.4.3 for more information.

NOTE: All maintenance and service work, including battery replacement, should be performed by qualified service personnel.

For authorized service personnel only:

Never short the battery terminals. Shorting may cause the battery to burn. Avoid charging in a sealed container. Proper disposal of batteries is required: refer to your local codes for disposal requirements. Never dispose of batteries in a fire: they may explode. Never disassemble or reassemble batteries; their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water, if eye contact occurs flush with water and contact a physician.

8.4Safety

CAUTION:

When the LP-U UPS is operating, all parts of the electronics are directly connected to the utility and high voltages are present on all internal parts, including the battery. Even after disconnection from the utility, all parts inside the UPS, including the battery, conduct dangerous voltages (except the RS232 output).

For your safety, only authorized service personnel may remove the cabinet cover.

8.5Storage

Always store the UPS in a dry location with the batteries in a fully charged state, storage temperature must be within -20 and +45° C. Storing the unit for a period exceeding 3 months can reduce the life of the batteries. To maintain their normal life expectancy, the batteries must be recharged periodically:

-if the storage temperature is within -20 and +30°C (-4°F and 86° F): every 6 months, for 24 hours,

-if the storage temperature is within -20 and +45°C (-4°F and 113° F): every 4 months, for 24 hours.

8.6Recycling the UPS at the end of service life

NOTE: This product has been designed to respect the environment, using materials and components respecting eco-design rules. It does not contain CFCs (Carbon Fluorine Chloride) of HCFCs (Halogen Carbon Fluorine Chloride).

GE Digital Energy, in compliance with environment protection recommends that the UPS equipment, at the end of its service life, must be recycled conforming to the local applicable regulations.

WARNING

The batteries contain lead, which is a dangerous substance for the environment. Therefore the batteries must be recycled correctly by specialized companies.

LX: OPM_LPU_11U_5K0_10K_1US_V030

38

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Image 40
Contents Digital Energy LP 11U Page Digital Energy LP Series Important Safety Instructions Interfacing Features Installation Important Safety InstructionsGeneral Storage BatteriesIntroduction WarrantyDescription Functional Explanation Principles of OperationAutomatic Bypass Switch Installation Package ContentsTransport Unpacking LocationOutput voltage UPS model 120V 208V 240V Utility voltage UPS model 120V 208V 240VUPS model Tightening torque force LP 5/68/10-11U Standard installation procedure LP 5/6-11U Installation procedure 120V input Bypass tap factory setting 208 Volt Available input voltages hardware modificationsInput voltage 208 or 240Vac Bypass tap changed to 240 VoltAvailable output voltages hardware modifications Input voltage 120Vac optional, 5/6kVA onlyOutput voltage 208Vac Output voltage 120Vac split-phase LP 5/6/8/10-11U Output tap changeOutput voltage 120Vac single phase Output voltage 220/230/240VacSetup Screens Input VoltageInput Voltage Change to Output VoltageLP 5/6/8/10-11U Installation of battery pack Installation of parallel operating LP-U UPSs Autorestart OFF Setting Mismatch Autorestart OFF Press EnterMaintenance ECO-modeNo-load shutdown Manual bypassOperation Description of Front and Rear PanelRear panel of the step-up transformer Rear panel Step-up transformerStart-up Selftest ProgressBattery 23C UseInput Line Autonomy Time Left Operating Time 0YEAR 29DAYSStatus and Alarm Menu On Line Alarm Press UPTemp TOO High Battery Depleted Battery Charger no Float Capacitor C1 Capacity LOWInverter OFF Service Screens Service MenuInput and Output not Synchronized Software Version R2.9 FAN Speed INV.DC +Automatic Bypass Enabled Tstamp Q4Language English Input Voltage Output Voltage Output FrequencyFrequency Range 2% PLL Lock Speed Normal FAN CurveQuick Battery Test Start Automatic Bypass Enabled Service Warning DisabledTest Screens Procedure Deep Battery TestCalibrate BAT Test Activated Other Features Overload protection in bypass modeShutdown Utility startSuperior Battery Management ECOAuto Restart OFF Press Enter Auto restart Interfacing Features RS232 / contact interface Emergency shutdown Relay Card optional Snmp Interface optionalOptional Features Extended RuntimePlug-in Cards RPA-Facility Redundant Parallel ArchitecturePDM Power Distribution Module Seismic anchorsMaintenance SafetyRecycling the UPS at the end of service life Cooling fanSelftest Failure Temp TOO High TroubleshootingSelftest Failure Q4 not OK Specifications UPS Type 11U 10-11UAutomatic Bypass Switch Enclosure Dimensions Conduit Box Center of GravityLP 5/6/8/10-11U installation drawings LP 5/6/8/10-11U 208-240V input LP 5/6-11U 120V input