Digital Energy™ LP Series
8 - Maintenance
8.1General
When used properly, the UPS is virtually maintenance free other than keeping the air inlets/outlets free from dust.
8.2Cooling fan
The expected operational life of the cooling fans is approximately 20,000 to 40,000 hours of continuous operation. A high ambient temperature will shorten this operational life.
8.3Batteries
The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the number of discharge cycles.
As a healthy battery is essential to the performance of the UPS, an automatic battery test is performed regularly to ensure failsafe operation (see section 5.4.1). When the condition of the battery is critical, the warning signal will be activated (buzzer 1x per 8 secs, and alarm message 'Replace battery', see 5.3.2). The batteries must be replaced as soon as possible. Please contact your dealer. Use only UL recognised batteries (BAZR2), valve
regulated types.
NOTE: under certain circumstances a manual battery test can result in a false alarm: please see section 5.4.2
'QUICK BATTERY TEST'.
Regular deep battery tests are advised in order to
NOTE: All maintenance and service work, including battery replacement, should be performed by qualified service personnel.
For authorized service personnel only:
Never short the battery terminals. Shorting may cause the battery to burn. Avoid charging in a sealed container. Proper disposal of batteries is required: refer to your local codes for disposal requirements. Never dispose of batteries in a fire: they may explode. Never disassemble or reassemble batteries; their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water, if eye contact occurs flush with water and contact a physician.
8.4Safety
CAUTION:
When the
For your safety, only authorized service personnel may remove the cabinet cover.
8.5Storage
Always store the UPS in a dry location with the batteries in a fully charged state, storage temperature must be within
-if the storage temperature is within
-if the storage temperature is within
8.6Recycling the UPS at the end of service life
NOTE: This product has been designed to respect the environment, using materials and components respecting
GE Digital Energy, in compliance with environment protection recommends that the UPS equipment, at the end of its service life, must be recycled conforming to the local applicable regulations.
WARNING
The batteries contain lead, which is a dangerous substance for the environment. Therefore the batteries must be recycled correctly by specialized companies.
LX: OPM_LPU_11U_5K0_10K_1US_V030 | 38 | GE DE LP 11U UPS: Installation / User Manual 3.0 (US) |